K = cooling factor units = seconds – GE Industrial Solutions EntelliPro ES User Manual

Page 124

Advertising
background image

CHAPTER 3: MOTOR PR OTECTION

3.12

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

 

 

 

 

M otor

Heating

Class 30

K = 1

Class 30

K = 2

Class 30

K = 3

Class 30

K = 4

Class 30

K = 5

Class 30

K = 6

Class 30

K = 7

Class 30

K = 8

Class 30

K = 9

Class 30

K = 10

Class 30

K = 11

Class 30

K = 12

Class 30

K = 13

Class 30

K = 14

Class 30

K = 15

100

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

90

108

216

324

432

540

648

756

864

972

1080

1188

1188

1188

1512

1620

80

228

456

684

912

1140

1368

1596

1824

2052

2280

2508

2508

2508

3192

3420

70

365

730

1095

1460

1825

2190

2555

2920

3285

3650

4015

4015

4015

5110

5475

60

523

1046

1569

2092

2615

3138

3661

4184

4707

5230

5753

5753

5753

7322

7845

50

709

1418

2127

2836

3545

4254

4963

5672

6381

7090

7799

7799

7799

9926

10635

40

938

1876

2814

3752

4690

5628

6566

7504

8442

9380

10318

10318

10318

13132

14070

30

1232

2464

3696

4928

6160

7392

8624

9856

11088

12320

13552

13552

13552

17248

18480

20

1647

3294

4941

6588

8235

9882

11529

13176

14823

16470

18117

18117

18117

23058

24705

10

2356

4712

7068

9424

11780

14136

16492

18848

21204

23560

25916

25916

25916

32984

35340

 

Figure 3-8: Thermal cooling model when trip curve is set to IEC class 30.

K = Cooling Factor
Units = seconds

Advertising