Pulsar Plus Controller Family

Issue 7 December 2011

160

sum

Report Statistics

Syntax:

sum obj,attr
where: obj,attr is an object-attribute pair defined by the following:
sum dc1,adcReport plant load current statistics
sum br1,hbtReport highest battery temperature statistics
sum br1,amtReport ambient temperature statistics

Description
This command reports the highest hourly a averages, highest hourly maximum, and the
highest hourly minimum statistics for plant load and highest battery temperature. The
following is an example of a command response:

* sum dc1,adc
:DC1 ADC
HHI=
30-MAY-03,12:03:00,127.3
14-FEB-03,11:15:37,126.9
24-DEC-03,02:30:13,126.2
LHI=
29-MAR-03,10:43:00,120.0
04-APR-03,11:15:53,121.1
21-SEP-03,07:13:10,124.3
HHA=
03-JAN-03,12:00:00,127.0
18-APR-03,11:00:00,126.5
21-OCT-03,02:00:00,126.1
.
*

The line “:DC1 ADC” indicates that the information that follows is for the plant load current.
The “HHI=” indicates highest hourly instantaneous reading. The “LHI=” indicates highest
hourly instantaneous reading. The “HHA=” indicates highest hourly average reading. The “.”
line is the end-of-command identifier. The “* ” in the example above is the user command line
prompt.

sum

Report Plant Load Trend Statistics

Syntax:

sum dct1

Description
This command reports the plant trend statistics, which includes up to 16 daily highest hourly
and lowest hourly instantaneous readings, up to 32 daily maximum hourly averages, and up to
13 monthly averages of the daily maximum hourly averages. The following is an example of a
command response:

* sum dct1
:DCT1
SRC=DC1 ADC
CLR=01-JAN-2001,12:00:00
DHI=
29-JAN-2002,02:00;00,123.2