Connect to the Controller

Step

Action

Table 4 Auxiliary Input Connector

Pin #

Wire Color

Signal Name

Description

1

(BK)

Aux Input 1
(Aux1)

Auxiliary input to monitor a contact closure or open to its
respective return on pin 8, Auxiliary Input Return. See
Appendix E for alarm assignments

2

(BR)

Aux Input 2
(Aux2)

Auxiliary input to monitor a contact closure or open to its
respective return on pin 8, Auxiliary Input Return. See
Appendix E for alarm assignments

3

(R)

Aux Power
Major Input
(AMJ)

Auxiliary input to monitor a contact closure to the non-
grounded side of a dc bus (±24V/-48V) to create the
standard Auxiliary Power Major alarm. See Appendix E for
alarm assignments

4

(O)

Plant Battery
Test/ Group
Standby/TR
(GSTR)

Dedicated input to be monitored for a contact closure to
its respective return on pin 9. Used for Plant Battery Test
and Group Standby Feature. Factory default as the Group
Standby feature upon a contact closure.

5

(Y)

Emergency
Power Off
(EPO)

Dedicated EPO input to be monitored for a contact closure
to its respective return on pin 10, Emergency Power Off
Return.

6

(G)

Aux Input 3
(Aux3)

Auxiliary input to monitor a contact closure or open to its
respective return on pin 8. See Appendix E for alarm
assignments.

7

(BL)

Aux Input 4
(Aux4)

Auxiliary input to monitor a contact closure or open to its
respective return on pin 8. See Appendix E for alarm
assignments.

8

(V)

Aux Input
Return
(Aux_R)

Return for Auxiliary Inputs 1-4.

9

(S)

Plant Battery

Test/ Group

Standby (TR)

Ret.(GSTR_R)

Return for Plant Battery Test and Group Standby.

10

(W)

Emergency

Power Off Ret.

(EPO_R)

Return for EPO input.