GE Industrial Solutions OKCV3000CN DeviceNet User Manual
Page 40
GEl- 100343
3) connect the DGFC to the DeviceNet network, power off and then on the system
ATTENTION:
maximum number of parameters read is 10
ATTENTION:
maximum number of parameters written is 10
ATTENTION:
since words 64 to 73 of FWA can be considered a single block, only word 64 (read it
with RFIX) has a valid time-out. Words from 65 to 73 have the same time-out as word
64. You should never check time-out of words 65. to 73.
ATrENTION:
since words 74 to 83 of FWA can be considered a single block, only word 64 (write it
with WFIX) has a valid time-out. Words from 75 to 83 have the same time-out as word
74. You should never check time-out of words 75 to 83.
AlTENTION:
before starting be sure that the number of parameters received and transmitted matches
on the DGFC and master. Otherwise unpredictable behavior can occur.
Hz
HOW TO CONNECT DGFC