1.4. MAIN FEATURES OF DEVICENET

These are the main features of DeviceNet:

-

upto64nodes;

-

3 selectable baud rates: 500, 250 and 125 kbaud;

-

linear topology;

-

distances between first and last node:

500 meters (1640 ft.) @ 125 kbaud

250 meters (820 ft.) @ 250 kbaud

100 meters (328 ft.) @ 500 kbaud

-

duplicate MACID detection;

-

trunk/drop line cable;

-

trunk line is the backbone (main line) of the cable system;

-

drop line is the cable that “hangs” from the trunk line and connects devices to the trunk line;

-

maximum drop line length is 6 meters;

-

cumulative drop line length is:

156 meters (512 ft.) @ 125 kbaud

78 meters (256 ft.) @ 250 kbaud

39 meters (128 ft.) @ 500 kbaud

-

trunk line is terminated by 120-ohms resistors on both ends;

-

shielded double twisted pair (power +signal);

-

cable is 5 wires: 2 for power, 2 for signal, 1 for shield

-

miswiring protection;

-

multimaster capabilities;

-

peer-to-peer;

-

node removal without severing the network;

-

CAN technology (built-in error management as CRC, stuff, form, etc. and Bus Off);

-

supports isolated and non-isolated nodes;

-

supports self-powered and network-powered nodes (simultaneously);

1.5. MAIN FEATURES OF THE—DGFC

These are the main DGFC DeviceNet features.

1

-

support of the Predefined Master/slave connection set. This allows the exchange up to 10 drive param-
eters in reading and 10 in writing with the master (usually a PLC, but a PC card can also be connected). In
this case the card is slave only. There are two sub-modes. The first is to use a DGFC as a communication
only card, the second to use aDGFC as a communication card and execute aBricks program simultaneously.

2

-

support of a LocalBus. By using some DeviceNet Bricks (or W-f-D blocks) you can connect a DGFC to
another DGFC (peer-to-peer), without using any other node (no PLC/PC required). Note that each node can
have up to 3 masters and many slaves at the same time.