Operating Manual ADVANCED SNMP WEB INTERFACE CARD

8.2.2 Details web page

Clicking in the “Details” page link, a similar screen will appear:

Meaning of the different fields present at the UPS Details page:

Battery Group

Battery Status:

Indication of the remaining capacity in the UPS system's batteries. A value of battery Normal indicates
that the remaining run-time is greater than LowBattTime (see UPS configuration page). A value of battery

Low indicates that the remaining battery run-time is less than or equal to Low BattTime (see UPS
configuration page). A value of battery Depleted indicates that the UPS will be unable to sustain the

present load when and if the utility power is lost (including the possibility that the utility power is
currently absent and the UPS is unable to sustain the output).

Second On battery:

If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time

since the network management subsystem was last restarted, whichever is less.
Zero shall be returned if the unit is not on battery power.

EstimatedMinuteRemain:

An estimate of the time to battery charge depletion under the present load conditions if the utility power
is off and remains off, or if it were to be lost and remains off.

EstimatedChargeRemain: An estimate of the battery charge remaining, expressed as a percent of full charge.

Battery voltage:

The value of the present battery voltage.

Battery current:

The present battery current.

Battery temperature:

The ambient temperature at or the temperature close to the UPS Battery.

Battery ripple:

The present DC link RMS voltage ripple.

Input Group

Phase:

The input line identifier.

Frequency:

The present input frequency.

Voltage:

The magnitude of the present input voltage.

Current:

The magnitude of the present input current.

True Power:

The magnitude of the present input true power.

Bad Input Line:

A count of the number of times the input entered an out-of-tolerance condition as defined by the
manufacturer. This count is incremented by one each time the input transitions from zero out-of-
tolerance lines to one or more input lines out-of-tolerance.

Output Group

Phase:

The output line identifier.

Voltage:

The magnitude of the present output voltage.

Current:

The magnitude of the present output current.

Power:

The present output true power.

Load:

The percentage of the UPS power capacity presently being used on this output line.

Power Factor:

The present output power factor. A positive value indicate an inductive load; a negative value indicate a
capacitive load; value 1 indicate a resistive load.

Note: the value may not be available in case of low UPS load.

Peak Current:

The present output peak current..

Share Current:

The present share component of the inverter output current into a parallel system; RMS value.

Output Source:

The present source of output power. The enumeration none indicates that there is no source of output
power (and therefore no output power), for example, the system has opened the output breaker.

Output frequency:

The present output frequency.

Bypass Group

Phase:

The bypass line identifier.

Voltage:

The present bypass voltage.

Current:

The present bypass current.

Power:

The present true power conveyed by the bypass.

Bypass Frequency:

The present bypass frequency.