Floor mounting – GE Industrial Solutions BDCBB H569-445 User Manual

Page 12

Advertising
background image

Secondary DC Power Distribution Bay H569-445

Issue 3 June 2012

12

Floor Mounting

When installing the BDFB cabinet to the floor, the following mounting hardware may be

required depending on customer requirements.

• Drill anchor holes to depth specified in table below.

• Place floor insulation pad and/or use insulation bushings provided with anchors

if required.

• Shim under cabinet corners as necessary to level.

• Torque anchors as specified in table below.

Anchor Kits

Seismic

Zone

Ordering

Code

Anchor Type

(Hilti)

Hole

Size

Wrench

Torque

0,1,2

847135662 (4) 1/2 inch

drop-in

5/8 inch bit
2” deep

3/4 inch

216 in·lbs
(18 ft·lbs)

24.5

N·m

0,1,2,3,4 847135688 (4) 12 mm

cap bolts

18mm bit
100mm deep

19 mm

720 in·lbs
(60 ft·lbs)

81.6

N·m

Isolation and Leveling Kits

Ordering Code

Description

408520408

Floor Insulation Kit (16 in x 24 ¼ in)

CC109121588 Shim Kit

Figure 3 Footprint of Cabinets