GE Industrial Solutions AF-300E$ User Manual
Page 77
Advertising
LCD
GRAPHIC
FACTORY
FUNCTION
DISPLAY
SETTING
DESCRIPTION
SETTING
6-20
OUTPUT TERMINAL FUNCTIONS
* 48
FAR HYSTR
FREQUENCY AT REFERENCE HYSTERESIS (WIDTH)
2.5
The signal is on when the output frequency
equals the frequency reference’s set point.
This is an open collector output and can be
used in conjuction with a relay unit to allow
connection to system control circuitry.
Adjustable from 0.0 to 10 Hz in 0.1 Hz steps.
* 49
FDT LEVEL
FREQUENCY DETECTION THRESHOLD
60
The signal is on when the output frequency
exceeds the detection level setting. This
is an open collector output and can be used
in conjuction with a relay unit to allow
connection to system control circuitry.
Adjustable from 0 to 400 Hz.
Far
Hyster
Far
Hyster
Far
Signal
t