Data Sheet

October 4, 2013

HW/HC004/005/006 Series DC-DC Power Module:

18-36Vdc & 36-75Vdc Input; 1.0V-5Vdc Output; 4A - 6A Output Current

LINEAGE

POWER

19

Thermal Considerations

The power modules operate in a variety of thermal
environments; however, sufficient cooling should be
provided to help ensure reliable operation.

Considerations include ambient temperature, airflow,
module power dissipation, and the need for increased
reliability. A reduction in the operating temperature of the
module will result in an increase in reliability. The
thermal data presented here is based on physical
measurements taken in a wind tunnel.

The thermal reference point, T

ref

used in the

specifications is shown in Figure 66. For reliable
operation this temperature should not exceed 115

o

C.

Figure 66. T

ref

Temperature Measurement Location.

Please refer to the Application Note “Thermal
Characterization Process For Open-Frame Board-
Mounted Power Modules” for a detailed discussion of
thermal aspects including maximum device
temperatures.

Heat Transfer via Convection

Increased airflow over the module enhances the heat
transfer via convection. Derating figures showing the
maximum output current that can be delivered by each
module versus local ambient temperature (T

A

) for natural

convection and up to 3m/s (600 ft./min) are shown in the
respective Characteristics Curves section.

EMC Considerations

The figure 67 shows a suggested configuration to meet
the conducted emission limits of EN55022 Class B.

Vin+

HW005

Vin-

Vout+

Vout-

L1 - CMC

C6 56nF

C5 56nF

C1
0.68uF

C4
33uF
100V

C2
0.68uF

Pulse P0354

C3
0.68uF

L2

10uH

Figure 67. Suggested Configuration for EN55022
Class B.

100K

500K

1M

5M

10M

30M

Frequency(Hz)

10

20

30

40

50

60

70

80

90

Lev

el

(

dB

µ

V

)

EN 55022 Class B Conducted Average dBuV

Figure 68.

EMC signature using above filter,

HW005A0F.

For further information on designing for EMC
compliance, please refer to the FLTR100V10 data sheet
(FDS01-043EPS).

Layout Considerations

The HW/HC005 power module series are low profile in
order to be used in fine pitch system card architectures.
As such, component clearance between the bottom of
the power module and the mounting board is limited.
Avoid placing copper areas on the outer layer directly
underneath the power module. Also avoid placing via
interconnects underneath the power module.

For additional layout guide-lines, refer to FLTR100V10
data sheet.