- 82 -

Item

Specifications

Remarks

Overload

Internal electronic thermal overload relay protects drive overload.

Overvoltage

Detect the excessive DC link circuit voltage to stop drive.

Overcurrent

Detect overcurrent due to overload on drive output side to protect drive

Incoming surge

Detect incoming surge voltage between AC power and the earth to protect

drive.

Undervoltage

Detect the DC link circuit undervoltage to stop drive

Overheating

Detects the cooling fan fault or abnormal temperature rise of drive to pro-

tect drive.

Short-circuit

Detect overcurrent due to short-circuit on drive output side to protect drive.

Ground fault

Detects overcorrect due to ground fault on drive output side to protect drive.

(Detect at starting)

Motor protection

Protect general-purpose motor with electronic thermal overload.

Input phase fail-
ure protection
(only for 3-phase
200V series)

The drive is protected against phase failure on the input side or over-current

due to inter-phase imbalance.

Stall prevention

Controls frequency to prevent OC trip in case of the output current exceeds

the limit value during acceleration.

Lowers the frequency to hold almost constant torque in case of the output

current exceeds the limit value during constant speed running.

Controls frequency to prevent OU trip in case of the DC link circuit voltage

exceeds the limit value during deceleration.

Retry

“Retry” function can be set for the protective functions OC1 to OC3 and

OU1 to OU3.(No. of times of retry: 5, waiting time: 0.5s fixed.

Dielectric
strength test

At 2000Vac for 1 min. between any main circuit terminals and

ground.(10mA or less)

Protection

Megger test

At 500Vdc megger test between any main circuit terminals and ground

(5M

or more)