3 from manual bypass (q2) to normal function vfi, From manual bypass (q2) to normal function vfi – GE Industrial Solutions SG Series 10 – 20 – 30 – 40 kVA Operating Manual User Manual
Page 45

Modifications reserved
Page 45/83
OPM_SGS_USM_10K_40K_0US_V030.doc
Operating Manual SG Series 10 –20 – 30 - 40 kVA
7.1.3 From Manual Bypass (Q2) to normal function VFI
Initial status:
Load supplied from Manual Bypass.
1. Close Q1 (Pos. I).
• Bypass connects to Load.
LED Load on Bypass lights up.
• Rectifier starts automatically and LED
in Rectifier symbol and LED Battery
charge light up.
2. Open Q2 (Pos. O).
• LED Manual Bypass turns OFF.
3. Connect the Battery to the UPS by closing the Battery Switch or Fuses, in case of
External Battery .
4. Press “inverter on” ( I ) key.
• Soft-start of Inverter, indicated with
blinking LED.
• At the end of Soft-start the LED
remains lit.
• Automatic transfer from Bypass to
Inverter.
• UPS output LED indicates Load on
Inverter.
The LCD must display on the main screen the status “LOAD ON INVERTER”.
END OF PROCEDURE