Xylem 19 001 200 R2 SILENT STORM VFD Pumping System User Manual

Page 26

Advertising
background image

24

even electrical arcing or that something
is in a bind? This can indicate a
serious problem.

b. There is going to be some harmonic

vibration with the pumps and motor.
We are looking for excessive vibration
or noise. Can you see a bend in the
pump shaft? Do the motor and shaft
shake violently? This needs servicing
immediately. Do not operate pump if
vibration is excessive.

c. Confirm that the building cooling and

ventilation systems are operating and
clear of all obstructions. Maximum
operating range for equipment is 40°C
(104°F). Verify that water, grease, oil,
hardware, etc. are not leaking or loose
on the pump station.

8. Verify that the area surrounding the pump

shaft at the pump head has some leakage
when the pump is operational.

a. The correct leakage rate is

approximately one drop per second. If
the leakage exceeds two drops per
second, the packing gears need to be
adjusted.

WARNING: Rotating Shaft Hazard

Packing adjustment should be performed by
properly trained and qualified personnel.

Failure to follow these instructions could result in
serious personal injury, death, or property
damage.

9. Station skid:

a. Visually inspect for leaks in the station

piping, valves, and other components.

b. Visually inspect the piping and skid for

any stress cracks in the welds.

c. Visually inspect the station for loose or

damaged paint or areas of rust.

DANGER: Personal Injury Hazard

Pump station maintenance must be performed by
properly trained and qualified personnel. Hazards
exist

for

electrocution,

shock,

rotating

components, and pressurized components.

Failure to follow these instructions will result in
death or serious injury.

WINTERIZING PUMP STATIONS

CAUTION: Equipment Damage Hazard

Your pumping system must be properly winterized
before storage. Failure to winterize the system
could result in damage to the pipes, valves,
pumps, or other components.

Failure to follow these instructions indicates a
potentially hazardous situation, which, if not
avoided, may result in property damage.

Generalized Instructions for All Pump
Stations

1. Turn all enclosure switches to the OFF

position.

2. Open (turn off) all electrical disconnects to

the pump station.

DANGER: Personal Injury Hazard

The pumping system must be disconnected from
the main power supply before attempting any
operation or maintenance on the electrical or
mechanical parts of the system.

Failure to follow these instructions will result in
death or serious injury.


3. Close all the station discharge isolation

valves.

4. Close the pump station inlet isolation

valves.

5. Close all auxiliary equipment isolation

valves (if applicable).

6. Remove all connections from the heat

exchanger inlet and discharge. Force
water from the heat exchanger core with
compressed air.