Xylem 19 001 200 R2 SILENT STORM VFD Pumping System User Manual

Page 30

Advertising
background image

28

and verify that the supply valve is open.

If equipped with a suction manifold strainer, clean as
required.

Ensure the supply piping not clogged or restricted.

Pressure is actually low – dynamic.

Ensure that the flow rate is less than the supply
capacity.

LOSS OF PRIME FAULT

Cause

Cure

Normally used on end-suction centrifugal pumps

System has lost prime or air is trapped in system.

Check the system for prime lead in the foot valve or
suction line.

Probe is dirty, corroded, or failed.

Clean or replace the probe as required.

Loss of prime relay failed.

To be performed by a qualified person only.
Check the relay for proper operation. Replace as
required.

PHASE FAULT

Cause

Cure

Previous power failure.

Press the station reset. If the problem is gone, the
fault will reset.

Incoming line voltage less than 90% of rated station
voltage.

Consult the power company.

Phase monitor voltage set too high.

To be performed by a qualified person only.
Example – monitor set at 480 V, try 460 V.

One or more dead legs on a 3-phase power line.

To be performed by a qualified person only.
Check all input fuses.

Call the power company.

A reversal, shift, or imbalance of the line phases.

Normally occurs after the power company has worked
on or replaced the transformer. Call the power
company.

Phase monitor failure.

To be performed by a qualified person only.
If the LEDs on the phase monitor are on, there is no
fault. If the LEDs are off, and all voltage and phase
conditions are good, the phase monitor needs to be
replaced.

VFD FAULT

Cause

Cure

Look at VFD keypad to determine specific fault and consult the VFD manual.

Codes identified below are some of the more common ABB 550 codes. Consult your specific VFD
manual for other drive applications.

Fault code 3 – dev overtemp (drive heatsink is
overheated).

To be performed by a qualified person only.
The VFD fan won’t come on. If there is no power, check
circuit breaker. Check for no continuity across transorb