Foundation requirements, Level the base on a concrete foundation – Xylem AquaForce Variable Speed Package System User Manual

Page 15

Advertising
background image

Guideline

Explanation/comment

Make sure that the space around the pump package is

sufficient.

This facilitates ventilation, inspection, maintenance, and

service.

If you require lifting equipment such as a hoist or tackle,

make sure that there is enough space above the pump

package.

This makes it easier to properly use the lifting equipment

and safely remove and relocate the components to a safe

location.

Protect the unit from weather and water damage due to

rain, flooding, and freezing temperatures.

This is applicable if nothing else is specified.

Do not install and operate the equipment in closed

systems unless the system is constructed with properly-

sized safety and control devices.

Acceptable devices:

• Pressure relief valves
• Compression tanks
• Pressure controls
• Temperature controls
• Flow controls

If the system does not include these devices, consult the

engineer or architect in charge before you operate the

pump.

Take into consideration the occurrence of abnormal noise

and vibration.

The best pump location for noise and vibration

absorption is on a concrete floor with subsoil underneath.

Foundation requirements

WARNING:
Electrical shock hazard. An electrical conduit installed below the surface may require a
corrosion-resistant protective coating in order to prevent conduit corrosion and electrical
shock. Failure to follow these instructions can result in serious personal injury, death, or
property damage.

Requirements

• The foundation must be able to absorb any type of vibration and form a permanent,

rigid support for the unit.

• The foundation must weigh at least 2-1/2 times the weight of the pump unit.
• Provide a flat, substantial concrete foundation in order to prevent strain and distortion

when you tighten the foundation bolts.

• Sleeve-type and J-type foundation bolts are most commonly used. Both designs allow

movement for the final bolt adjustment.

• Tie the concrete pad in with the finished floor.

Level the base on a concrete foundation

1. Place the pump package on its concrete foundation.
2. Place 1.00 in./(25.40 mm) thick steel shims or wedges on both sides of each anchor

bolt in order to support the pump package.
Make sure you also place the shims or wedges midway between the bolts.
This also provides a means of leveling the base.

Installation

AquaForce Variable Speed Package System Mechanical Installation, Operation, and Maintenance Manual