Xylem IM009 R02 Model 3657/3757 User Manual

Page 3

Advertising
background image

3

DANGER

WARNING

CAUTION

WARNING

Hazardous voltage

can shock, burn or

cause death.

SAFETY INSTRUCTIONS

TO AVOID SERIOUS OR FATAL PERSONAL

INJURY OR MAJOR PROPERTY DAMAGE, READ

AND FOLLOW ALL SAFETY INSTRUCTIONS IN

THE MANUAL AND ON THE PUMP.

This is a SAFETY ALERT SYMBOL.When

you see this symbol on the pump or in the

manual, look for one of the following signal

words and be alert to the potential for per-

sonal injury or property damage.
Warns of hazards that WILL cause

serious personal injury, death or major

property damage.
Warns of hazards that CAN cause serious

personal injury, death or major property

damage.
Warns of hazards that CAN cause per-

sonal injury or property damage.

NOTICE: INDICATES SPECIAL INSTRUCTIONS

WHICH ARE VERY IMPORTANT AND MUST BE

FOLLOWED.
THIS MANUAL IS INTENDED TO ASSIST IN

THE INSTALLATION AND OPERATION OF

THIS UNIT. THOROUGHLY REVIEW ALL

INSTRUCTIONS AND WARNINGS PRIOR TO

PERFORMING ANY WORK ON THIS PUMP.
MAINTAIN ALL SAFETY DECALS.

Install, ground and wire accord-

ing to local and National Electri-

cal Code Requirements.
Install an all leg disconnect

switch near the pump.
Disconnect and lockout electrical

power before installing or servic-

ing the pump.
Electrical supply must match motor’s

nameplate specifications. Incorrect

voltage can cause fire, damage motor

and void the warranty.

Single phase pump motors are equipped with an au-

tomatic thermal protector, which opens the motor’s

electrical circuit when an overload condition exists.

This can cause the pump to start unexpectedly.

DESCRIPTION and SPECIFICATIONS

The Models 3657 (close-coupled) and 3757 (frame-

mounted) are single-stage end-suction pumps designed

for ultra-pure water systems, O.E.M. applications, food

and beverage processing and chemical services not de-

manding ANSI standard equipment.
The pumps have fully enclosed, investment cast, AISI

TYPE 316 stainless steel impellers, key driven and held in

position by an o-ring sealed locknut. The full volute cas-

ings are also investment castings of AISI TYPE 316 stain-

less steel, back pull-out configuration, with connections

for mating with standard 150 lb. ANSI flanges. Shafts are

protected with o-ring sealed stainless steel sleeves. Shaft

sealing is with mechanical seal.

Close-coupled units have NEMA frame motors, C-face

mounting, JM shaft extension. Frame mounted units can

be coupled to motors through a spacer coupling, or belt

driven.

1. Important:

1.1. Inspect unit for damage. Report any damage to car-

rier/dealer immediately.

1.2. Electrical supply must be a separate branch circuit

with fuses or circuit breakers, wire sizes, etc. per

National and Local electrical codes. Install an all-leg

disconnect switch near pump,

ALWAYS DISCONNECT ELECTRICAL

POWER WHEN HANDLING PUMP

OR CONTROLS.

1.3. Motors must be wired for proper voltage. Motor

wiring diagram is on motor nameplate. Wire size

must limit maximum voltage drop to 10% of name-

plate voltage at motor terminals, or motor life and

pump performance will be lowered.

1.4. Always use horsepower-rated switches, contactors

and starters.

1.5. Motor Protection:

1.5.1. Single-phase: Thermal protection for single-

phase units is sometimes built in (check nameplate).

If no built-in protection is provided, use a contactor

with a proper overload. Fusing is permissible.
1.5.2. Three-phase: Provide three-leg protection

with properly sized magnetic starter and thermal

overloads.

1.6. Maximum Operating Limit(s):

Liquid Temperature: 212°F (100°C) with standard seal.

250°F (120°C) with optional

high temp. seal.

Pressure:

175 PSI.

Starts per Hour:

20, evenly distributed.

1.7. Regular inspection and maintenance will increase

service life. Base schedule on operating time. Refer

to Section 8.

2. Installation:

2.1. General

2.1.1. Locate pump as near liquid source as possible

(below level of liquid for automatic operation).
2.1.2. Protect from freezing or flooding.
2.1.3. Allow adequate space for servicing and

ventilation.
2.1.4. All piping must be supported independently of

the pump, and must “line-up” naturally.

CAUTION: NEVER DRAW PIPING INTO PLACE BY

FORCING THE PUMP SUCTION AND

DISCHARGE CONNECTIONS.

2.1.5. Avoid unnecessary fittings. Select sizes to keep

friction losses to a minimum.
2.1.6. After the piping is complete, rotate the unit by

hand to check for any binding.

2.2. Close-Coupled Units:

2.2.1. Units may be installed horizontally, inclined or

vertically.

WARNING

Hazardous

voltage