Description and Specifications

This Self-Priming – Centrifugal Pump is designed to

pump muddy water with minute quantities of suspended

solids. When pumping water, the pumps are self priming

on static suction lifts up to 25 feet (7.6 meters), while

with liquids which foam or foam emulsions, the static

suction lift is reduced to 10 feet (3 meters). A cast iron

impeller with solids handling capabilities is used.

THIS PUMP IS DESIGNED TO PUMP

WATER. NEVER USE THIS SELF

PRIMING PUMP TO PUMP FUEL,

FLAMMABLE, CORROSIVE OR

COMBUSTIBLE LIQUIDS. PUMPING

ABRASIVE LIQUIDS IS ALSO HAZ-

ARDOUS. IF IN DOUBT, CONSULT

FACTORY FOR PROPER USE AND

APPLICATION.

1. Important Safety Precautions

BEFORE USING YOUR SELF-PRIM-

ING – CENTRIFUGAL PUMP, READ

AND FOLLOW THESE SAFETY PRE-

CAUTIONS.

1. Never use these pumps for pumping flammable liq-

uids such as diesel or gasoline.

2. Before starting the pumps, follow all of the instruc-

tions in this manual and any supplemental instruc-

tions supplied with the pump.

3. Any person operating this pump and its power unit

should be fully aware of its safe operation before they

start using it.

4. Never operate an engine driven unit in an explosive

atmosphere, near combustible materials, or where

insufficient ventilation exists unless specific provi-

sions have been made regarding the power unit so

as to prevent possible injury and damage. Be certain

the power unit is safe for the area in which it is to be

operated.

5. Always be sure the unit is on a secure footing. Keep

the immediate pump area free of all unauthorized

personnel. If the pump is sitting beside a pit, be sure

it is well anchored so that it does not fall in.

6. Never operate the unit with any guards removed.
7. Do not overtighten the drain or filler plugs.Excessive

force may damage the threads or the pump body.

8. With engine driven pumps: A) Observe all safety pre-

cautions for the handling of fuel. B) Never refuel the

engine while running. C) Never refuel a hot engine.

D) Run engine only in well ventilated areas.

9. Before working on this pump make sure the power

unit cannot inadvertently be started.

10. Be sure the power unit, pump, wiring and piping

installations are suitable for the liquid being pumped

and comply with all applicable codes and regulations.

11. Use at least 12" (300 mm) of flexible hose to make

plumbing connections to the pump body. Rigid pip-

ing may put stresses on the pump, causing damage. If

rigid piping must be used, properly support it so as to

eliminate stresses on the pump.

12. Do not run the pump dry. Always fill the pump body

with water before starting. It is not necessary to drain

the pump body after use, unless there is danger of

freezing, settling of solids, or crystallization.

13. Do not subject pump to extreme conditions of acidity

or basicity. Consult factory for specific recommenda-

tions concerning chemicals and temperatures.

14. Only use original spare parts.

2. Before Starting

2.1 A suction strainer should be attached to the suction

hose or pipe. It is provided with holes or slots small

enough to prevent big stones, etc., from working

through and damaging the pump. Keep the strainer

clean. If possible, suspend the strainer to keep it from

working into the sediment. Or,

A) Prepare a bed of stones on which to rest the strainer.

B) Tie the strainer inside a basket or pail.

2.2 Fill the engine crankcase and air cleaner with oil as

specified in the Engine Manual.

2.3 FUEL: Regular gasoline (leaded or unleaded) which

can be mixed to the extent of 10% by volume with

ethanol. DO NOT use methanol.

2.4 Fill the pump with water through the priming port

on the top of the pump. Remember the pump is self-

priming only when the pump is filled.

2.5 Make certain that all hose and pipe connections are

airtight.

IMPORTANT: An air leak in the suction line may

prevent priming and will reduce the

capacity of the pump. Use sealant on all

threaded connections.

WARNING

CAUTION

Table of Contents

SUBJECT

PAGE

Important Safety Precautions ......................................... 2
Before Starting .............................................................. 2
Operating Instructions ................................................... 3
Repair Parts ................................................................... 3
Troubleshooting ............................................................ 4
Goulds Water Technology Limited Warranty ................. 4

Owner’s Information

Please fill in data from your pump nameplate.

Warranty information is on page 4.
Pump Model:

Serial Number:
Dealer:
Dealer’s Phone Number:
Date of Purchase:
Installation Date: