Danger – Xylem IM103 R03 5 and Larger Submersible Pump User Manual

Page 6

Advertising
background image

6

3.2 Splice Drop Cable to Motor Leads

When the drop cable must be spliced or connected to the

motor leads it is necessary that the splice be watertight. The

splice can be done with heat shrink kits, compression fittings,

or waterproof tape. Match motor leads and drop cable by

color codes or identify drop cable wires to insure a proper

connection at the control box.

A. Heat Shrink Splice Instructions

To use a typical heat shrink kit: strip ½" from the motor

wires and drop cable wires, it is best to stagger the splices.

Place the heat shrink tubes on the wires. Place the crimps

on the wires and crimp the ends. Slide the heat shrink

tubes over the crimps and heat from the center outward.

The sealant and adhesive will ooze out the ends when the

tube shrinks. The tube, crimps, sealant, and adhesive

create a very strong, watertight seal. Overheating may

burn the heat shrink tubes.

B. Taped Splice Instructions

1) Strip individual conductor of insulation only as far as

necessary to provide room for a stake type connector.

Tubular connectors of the staked type are preferred. If

connector O.D. is not as large as cable insulation,

build-up with rubber electrical tape.
2) Tape individual joints with rubber electrical tape, using

two layers; the first extending two inches beyond each

end of the conductor insulation end, the second layer two

inches beyond the ends of the first layer. Wrap tightly,

eliminating air spaces as much as possible.
3) Tape over the rubber electrical tape with #33 Scotch

electrical tape, or equivalent, using two layers as in step

“B” and making each layer overlap the end of the

preceding layer by at least two inches.

C. Compression Splice Kits

Consult instructions supplied with compression splice kits

or consult your local supplier.

3.3 Mounting the Motor Control Box

Single phase 3-wire control boxes are suitable for vertical

mounting in indoor or outdoor locations. They will operate

at temperatures between 14ºF ( -10º C) and 122º F (50º C).

Select a shaded, dry place to mount the box. Insure that there

is enough clearance for the cover to be removed.

3.4 Verify Voltage

Insure that motor nameplate voltage and power supply

voltage are the same. Three-phase starter coils are very

voltage sensitive, always verify actual supply voltage with

a voltmeter. High or low voltage will damage motors and

controls and is not covered under warranty.

3.5 Turn Supply Power Off

Use a disconnect switch where required by code. Turn the

circuit breaker OFF and lock-out the disconnect switch in

the OFF position to prevent accidentally starting the pump

before you are ready.

3.6 Make Connection to Single Phase (1Ø)

Control Box or Three Phase (3Ø) Starter

Do not power the unit or run the pump until all electrical

and plumbing connections are completed. Exception – to

verify 3 phase motor rotation, it is acceptable to power the

motor before it is attached to the water end to verify cor-

rect rotation. After checking rotation lock-out disconnect or

circuit breaker in OFF position!

Verify that the disconnect or breaker is OFF before mak-

ing any connections to the power supply. Always follow the

National Electric Code (N.E.C.) in the U.S., or the Canadian

Electrical Code in Canada, as well as all state, provincial, or

local codes.

A. Single Phase (1Ø) Three-Wire Control Box Wiring

Connect the color coded motor leads to the motor

control box terminals –

Y (yellow), R (red), and B (black); and the Green or bare

wire to the green ground screw.
Connect wires between the Load terminals on the pres-

sure switch and control box terminals L1 and L2. Run a

ground wire between the switch ground and the control

box ground. See Fig. 7 or 8

B. Three Phase (3Ø) Starter Wiring

Connect the motor leads to T1, T2, and T3 on the 3

phase starter. Connect the ground wire to the ground

screw in the starter box. Follow starter manufacturers

instructions for connecting pressure switch (where used)

to starter. See Fig. 9 or 10

3.7 Make Power Supply Connection

Provide a separate fused or circuit breaker protected branch

circuit for the pump. Install a main disconnect switch in full

view and easily accessible from the pressure switch and tank

location.

Single phase:

With pressure switch – make the connection from the pres-

sure switch Line terminals to the disconnect switch (where

used) and then to the circuit breaker panel.
Without pressure switch – make the connection from the

control box L1 and L2 terminals to the disconnect switch

(where used) and then to the circuit breaker panel.

Three phase - make the connections between L1, L2, L3, and

ground on the starter to the disconnect switch and then to

the circuit breaker panel.

CAUTION

DANGER

CAUTION

CAUTION

Advertising