Xylem IM226R02 CP-Series Submersible Motors User Manual

Page 17

Advertising
background image

CP-Series Submersible Motors Installation, Operation and Maintenance Manual

15

TABLE 2 — 8" Three Phase Motors, 380 and 460 volt

Motor

Rated Rated

Operating Characteristics

Direct On-Line Service SF

SF

Type

Power Voltage

At Rated Power

Starting

Factor Watts Amps

Three HP kW V kW A RPM EFF PF Is Ts Tmax SF kW A

Phase

/In

/Tn

/Tn

P8..40T386A

40 30

380

37.0

67.8

3470 81.5 0.83 5.50 1.04 2.22 1.15 43.0

78.0

P8..40T466A

460

56.0

64.4

P8..50T386A

50 37

380

45.6

83.5

3475 81.5 0.83 5.26 1.04 2.23 1.15 53.5

96.1

P8..50T466A

460

69.0

79.4

P8..60T386A

60 45

380

54.2

99.3

3480 83.0 0.83 4.98 0.98 2.22 1.15 62.0

114

P8..60T466A

460

82.0

94.3

P8..70T386A

70 52

380

62.7

116

3475 83.0 0.82 5.56 1.06 2.22 1.15 73.0

134

P8..70T466A

460

96.0

110

P8..75T386A

75 55

380

66.1

121

3475 83.5 0.83 5.44 1.06 2.24 1.15 77.5

139

P8..75T466A

460 100 115

P8..80T386A

80 60

380

71.6

130

3480 84.0 0.84 5.07 1.04 2.23 1.15 83.0

149

P8..80T466A

460 107 123

P8..90T386A

90 67

380

80.0

146

3480 84.0 0.83 5.13 1.03 2.23 1.15 95.0

168

P8..90T466A

460 121 139

P8..100T386A

100 75

380

89.7

162

3485 84.0 0.84 5.04 1.01 2.22 1.15 108

187

P8..100T466A

460 134 154

P8..110T386A

110 83

380

99.1

179

3485 84.0 0.84 4.79 0.97 2.28 1.15 118

206

P8..110T466A

460 148 170

P8..125T386A

125 93

380

111

201

3490 84.0 0.84 4.60 1.02 2.22 1.15 129

231

P8..125T466A

460 166 191

Ts/Tn = ratio between starting torque and nominal torque.

Is/In = ratio between starting and FL amps.

Tmax/Tn = ratio between maximum torque and nominal torque.

TABLE 3 — 10" Three Phase Motors, 380 and 460 volt

Motor

Rated Rated

Operating Characteristics

Direct On-Line Service SF

SF

Type

Power Voltage

At Rated Power

Starting

Factor Watts Amps

Three HP kW V kW A RPM EFF PF Is Ts Tmax SF kW A

Phase

/In

/Tn

/Tn

P10..125T386A

125 93

380

110

199

3510 85.0 0.84 5.55 1.02 2.22 1.15 130

229

P10..125T466A

460 164 189

P10..150T386A

150 110

380

131

242

3520 85.5 0.82 6.38 1.43 2.19 1.15 149

272

P10..150T466A

460 200 225

P10..175T386A

175 130

380

152

286

3520 85.5 0.81 6.31 1.50 2.22 1.15 174

328

P10..175T466A

460 236 271

P10..200T386A

200 150

380

176

329

3525 85.5 0.81 6.24 1.56 2.22 1.15 191

379

P10..200T466A

460 272 313

Ts/Tn = ratio between starting torque and nominal torque.

Is/In = ratio between starting and FL amps.

Tmax/Tn = ratio between maximum torque and nominal torque.