Xylem IM234 R01 9K585 Moisture Sensor Relay User Manual

Page 2

Advertising
background image

2

1: SAFETY INSTRUCTIONS

TO AVOID SERIOUS OR FATAL PERSONAL INJURY

OR MAJOR PROPERTY DAMAGE, READ AND

FOLLOW ALL SAFETY INSTRUCTIONS IN MANUAL

AND ON EQUIPMENT.
THIS MANUAL IS INTENDED TO ASSIST IN THE

INSTALLATION AND OPERATION OF THIS UNIT

AND MUST BE KEPT WITH THE UNIT.

This is a SAFETY ALERT SYMBOL.

When you see this symbol on the pump,

the controller or in the manual, look for

one of the following signal words and

be alert to the potential for personal

injury or property damage.
Warns of hazards that WILL cause

serious personal injury, death or major

property damage.
Warns of hazards that CAN cause serious

personal injury, death or major property

damage.
Warns of hazards that CAN cause

personal injury or property damage.

NOTICE:

INDICATES SPECIAL

INSTRUCTIONS WHICH ARE

VERY IMPORTANT AND MUST BE

FOLLOWED.
THOROUGHLY REVIEW ALL INSTRUCTIONS

AND WARNINGS PRIOR TO PERFORMING ANY

WORK ON THIS CONTROLLER.
MAINTAIN ALL SAFETY DECALS.

DANGER

WARNING

CAUTION

WARNING

WARNING

1: SAFETY INSTRUCTIONS

WARNING

Disconnect and lockout electrical power

before installing or servicing any

electrical equipment.

ELECTROCUTION HAZARD.

CONTROLLER INPUT GROUND

TERMINAL (GND) AND ALL EXPOSED METAL

PIPING, INCLUDING PRESSURE TRANSDUCER

CASE, MUST BE CONNECTED TO THE SERVICE

ENTRANCE GROUND TERMINAL.

All electrical work must be performed

by a qualified technician. Always follow

the National Electrical Code (NEC), or the Canadian

Electrical Code, as well as all local, state and provincial

codes. Code questions should be directed to your local

electrical inspector. Failure to follow electrical codes and

OSHA safety standards may result in personal injury or

equipment damage. Failure to follow manufacturer’s

installation instructions may result in electrical shock,

fire hazard, personal injury or death, damaged

equipment, unsatisfactory performance, and may void

manufacturer’s warranty.

5VDC MOISTURE SENSOR RELAY

MODEL #9K585

INSTALLATION INSTRUCTIONS
The Sensor can detect the presence of water and provide

a relay output for signal or control of an external device.
The switch operates on 5 Volts DC and functions as a
Normally Closed Sensor, for a Closed Loop system. The
Red and Balck wires power the switch while the White
and Green wires are the relay output wires.

For installation to an alarm panel, the Red wire is
connected to the positive side of a 5 Volt supply and the

Black wire is connected to the negative. The Green and
White wires can then be connected to any pre-selected
Closed Loop zone. A resistor can be connected in series
with either the Green or White wire for those panels that
require end-of-line resistance.
After installation these units should be tested with a
damp sponge or paper towel and inspected annually. If
there is any corrosion or damage the sensor should be
replaced.

5VDC MOISTURE SENSOR RELAY

SPECIFICATIONS
Power Requirements:
Operating Voltage

5 Volts DC

Operating Current

10 mA

Contact Characteristics:
Contact Resistance

100 mΩ

Switching Voltage

30 Volts DC Max

Switching Current

500 mA Max

Power

250 mW Max

Wire Connections:
Red

5 Volts DC

Black

- Ground

Green

Relay Contact

White

Relay Contact