5

wastewater pumps contain on-winding overloads, unless

noted on the pump nameplate. See Figure 1.
SINGLE PHASE CONTROL PANELS:

Control panels are available as Simplex (controls 1 pump)

or Duplex (controls 2 pumps). Our standard SES Series

Panels are available with many standard features and can

be built with our most popular options. We also custom

build panels which offer many more design options than

the SES panels. Custom control panels are available in many

different configurations. Custom panel quote requests may

be forwarded to Customer Service through any authorized

distributor.
Our “SES” Duplex panels feature a solid-state printed

circuit board design with standard high level alarm circuits.

Other standard features are: an auxiliary dry alarm con-

tact for signaling a remote alarm and float switch position

indicator lights.

INSTALLATION

Connect the pump(s) to the guide rail pump adapters or to

the discharge piping. Slide rail bases should be anchored to

the wetwell floor.
Complete all wiring per the control panel wiring diagrams

and NEC, Canadian, state, provincial and/or local codes.

This a good time to check for proper rotation of the mo-

tors/impellers.

DO NOT PLACE HANDS IN PUMP

SUCTION WHILE CHECKING

MOTOR ROTATION. TO DO SO

WILL CAUSE SEVERE PERSONAL

INJURY.
Always verify correct rotation. Correct

rotation is indicated on the pump casing.

Three phase motors are reversible. It is

allowable to bump or jog the motor for a

few seconds to check impeller rotation. It

is easier to check rotation before installing

the pump. Switch any two power leads to

reverse rotation.

Lower the pump(s) into the wetwell.
Check to insure that the floats will operate freely and not

contact the piping.

OPERATION

Once the piping connections are made and checked you can

run the pumps.
Piggyback Switch Operation – Plug the piggyback switch

into a dedicated grounded outlet and then plug the pump

into the switch. Test the pump by filling the wetwell until

the pump goes On. If the pumps run but fail to pump, they

are probably air locked, drill the relief holes per the instruc-

tions in the Piping Section.
Check the operating range to insure a minimum one minute

run time and that the pump goes Off in the correct position.
Control Panel Operation – Fill the wetwell with clear water.
Use the pump H-O-A (Hand-Off-Automatic) switches in

Hand to test the pumps. If they operate well in Hand pro-

ceed to test Automatic operation. If the pumps run but fail

to pump, they are probably air locked, drill the relief holes

per the instructions in the Piping Section.

These wide-angle, pump down switches may be used as

direct connected pump switches or as control switches.
SETTING THE FLOAT SWITCHES

There are no absolute rules for where to set the float

switches, it varies from job to job.
Suggested Rules to Follow:

All floats should be set below the Inlet pipe!
Off Float: Best:
set so the water level is always above the

top of the pump (motor dome). Next Best: set so the wa-

ter level is not more than 6" below the top of the pump.
On Float: set so the volume of water between the On and

Off floats allows pumps of 1½ HP and under to operate

for 1 minute minimum. Two (2) HP and larger pumps

should run a minimum of 2 minutes. Basin literature

states the gallons of storage per inch of basin height.
Lag/Alarm Float(s): should be staggered above the Off

and On floats. Try to use most of the available storage

provided by the basin, save some space for reserve stor-

age capacity. See Diagrams and Charts in Float Switch

Chart Section.
PANEL WIRING DIAGRAMS

Our control panels are shipped with instructions and wir-

ing diagrams. Use those instructions in conjunction with

this IOM. Electrical installation should be performed

only by qualified technicians. Any problem or questions

pertaining to another brand control must be referred

to that control supplier or manufacturer. Our technical

people have no technical schematics or trouble shooting

information for other companies' controls.
ALARMS

We recommend the installation of an alarm on all Waste-

water pump installations. Many standard control panels

come equipped with alarm circuits. If a control panel is

not used, a stand alone high liquid level alarm is avail-

able. The alarm alerts the owner of a high liquid level in

the system so they can contact the appropriate service

personnel to investigate the situation.
SINGLE PHASE PUMPS

Single phase (1Ø) pumps may be operated using a pig-

gyback or hard wired float switch, a contactor, or a Simplex

or Duplex control panel. See Figures 1 and 4.
All

1

/

3

and ½ HP, 115 or 230 volt pumps, and some ¾ and 1

HP pumps, are supplied with plug style power cords. They

may be plugged into piggyback float switches for simple

installations. It is allowable to remove the plugs in order

to hardwire or connect to a Simplex or Duplex controller.

Removing the plug neither voids the warranty nor violates

the agency Listings. See Figure 4.

PLUG-CONNECTED UNITS MUST

BE CONNECTED TO A PROPERLY

GROUNDED, GROUNDING TYPE

RECEPTACLE.
ON NON-PLUG UNITS, DO NOT

REMOVE CORD AND STRAIN RELIEF.

DO NOT CONNECT CONDUIT TO

PUMP.

Pumps with bare lead power cords can be hard-wired to a

float switch, wired to a 1Ø contactor, a Simplex controller

or a Duplex controller. Always verify that the float switch

is rated for the maximum run amperage, maximum starting

amperage, and the HP rating on the pump. Single-phase

WARNING

Hazardous voltage

can shock, burn or

cause death.

DANGER

Hazardous Machinery

!