INSULATION RESISTANCE READINGS

Normal Ohm and Megohm Values between all leads and ground

Condition of Motor and Leads

Ohm Value

Megohm Value

A new motor (without drop cable).

20,000,000 (or more)

20 (or more)

A used motor which can be reinstalled in well.

10,000,000 (or more)

10 (or more)

Motor in well. Readings are for drop cable plus motor.

New motor.

2,000,000 (or more)

2 (or more)

Motor in good condition.

500,000 - 2,000,000

.5 - 2

Insulation damage, locate and repair.

Less than 500,000

Less than .5

Insulation resistance varies very little with rating. Motors of all HP, voltage and phase ratings have similar values of

insulation resistance.
Insulation resistance values above are based on readings taken with a megohmmeter with a 500V DC output.

Readings may vary using a lower voltage ohmmeter, consult factory if readings are in question.

ENGINEERING DATA

PUMP OPERATION

Figure 2

Determining Pumping Range

Figure 1

Pumpmaster and Pumpmaster Plus - Hard Wired

Engineering data for specific models may be found in your catalog and on our website (address is on the cover).

Control panel wiring diagrams are shipped with the control panels. Please use the control panel drawings in
conjunction with this instruction manual to complete the wiring.

Minimum Submergence

Continuous
Duty

Fully Submerged

Maximum Fluid Temperature

Continuous
Operation

200º F 93º C

6" (15.3 cm)

6" (15.3 cm)

8" (20.3 cm) TURN ON LEVEL

WEIGHT

Single-Action Float Switch

"Typical" Installation

Figure 3

Pumping

range

Wide-Angle Float Switch

Piggyback

switch plug

Pump plug

Figure 4