Aquavar – Xylem IM154 R01 AQUAVAR User Manual

Page 6

Advertising
background image

5

AQUAVAR

Pin Connection
(to display)

40 Pin Connection

(to power board)

DIP - Switch
SW 4

24VDC Output
(max. 800mA)
for External Fan

RS485
Terminals

Motor Connection

Control Terminal Block

Main Supply

ATTENTION

Main Parts of the Control Board

(PN# 2509641)

Dip-Switch on the Controller Board
SW4: DIP-Switch to Select the Switching Frequency

Before switching, disconnect the power supply, otherwise
the AQUAVAR could be destroyed.

SW 4

Switching Frequency

1

2

OFF

OFF

8 kHz (Standard)

ON

OFF

5 kHz

OFF

ON

4 kHz

ON

ON

2.5 kHz*

*Recommended for submersible motors.

NOTE

Lower switching frequencies reduce heat in motor,
but increase audible noise.

For complete wiring procedures, refer to page 18 of IM043R07.
For complete programming procedures, refer to page 26 of IM043R07.

SW 4

2

1

8