Xylem MM 414B Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications User Manual

Page 3

Advertising
background image

3

BURNER

CUT-OFF LEVEL

AT CAST LINE

(22mm)

BURNER OFF

BURNER ON

7

/

8

"

PUMP

OFF

BURNER

OFF

BURNER

CUT-OFF LEVEL

AT CAST LINE

2

1

/

16

"

(52 mm)

NORMAL BOILER

WATER LINE

1

3

/

16

"

(30 mm)

PUMP OFF

PUMP ON

NORMAL BOILER

WATER LINE

When the water level in the boiler drops below the
middle probe, the circuit is broken which will acti-
vate the pump relay. When the water level rises
above the top probe, the circuit is made and the
pump relay is deactivated.

The distance between the top and middle probes is
adjustable. By turning the flange one bolt hole
clockwise, the distance can be increased by 7/16”.

When the water level in the boiler drops below the
bottom probe, the circuit is broken which will deacti-
vate the burner relay. When the water level is
restored to the middle probe, the burner relay will
be activated for auto reset controls only.

SWITCH SETTINGS:
Values are ±

3

/

16

” (6mm).

Flange in “B” Position

Flange in “A” Position

Burner Off has adjustable 0-60 second time delay.

Approximate

Distance Above

Cast Line

Differential

Setting

In. (mm)

In. (mm)

Pump Off

1

5

/

8

(41)

3

/

4

(19)

Pump On

7

/

8

(22)

Burner On

7

/

8

(22)

7

/

8

(22)

Burner Off

0

(0)

BURNER

CUT-OFF LEVEL

AT CAST LINE

(22mm)

BURNER OFF

BURNER ON

7

/

8

"

PUMP

OFF

BURNER

OFF

BURNER

CUT-OFF LEVEL

AT CAST LINE

1

5

/

8

"

(41mm)

NORMAL BOILER

WATER LINE

3

/

4

"

(19 mm)

PUMP OFF

PUMP ON

NORMAL BOILER

WATER LINE

Burner Off has adjustable 0-60 second time delay.

Approximate

Distance Above

Cast Line

Differential

Setting

In. (mm)

In. (mm)

Pump Off

2

1

/

16

(52)

1

3

/

16

(30)

Pump On

7

/

8

(22)

Burner On

7

/

8

(22)

7

/

8

(22)

Burner Off

0

(0)