H-335 – Xylem H-335 User Manual

Page 10

Advertising
background image

1-6 Introduction

H-335

1.6 Installation

Since the H-335 is a gravity referenced tilt sensor, it can be installed anywhere on the gate structure. The

H-335 must be installed exactly vertical and in the plane the tainter gate rotates. If the H-335 is not vertical

the senor will suffer an off-axis trigonemetric error as the gate is raised. The mount clamp has a 2-axis

gimbal which allows the inclinometer to be adjusted to compensate for camber in the gate structure.

The best place to install the sensor is near the trunnion bearing between the I-beam of the gate arm and the

concrete pier. Either the left or right arm will work. This location is protected from direct sunlight, logs and

debris, and allows for a short cable. The beam clamps allow easy installation with no drilling and will work

for beams up to 2.0 inches thick. Make certain the cable has sufficient slack for the entire rotation of the

gate.

The UserAngleSlope coefficient in the H-335 must be programmed appropriately depending on whether the

H-335 is installed on the left or right arms of a gate and whether on the inside or outside of the I-beam (see

Figure 2).

1.7 Making Connections to the H-335

Since the H-335 is normally exposed to the sun and weather, a cable rated for water immersion and

sunlight resistance is required. A black urethane or similar sunlight/waterproof rated cable is recommended.

Make certain the power is OFF before making any connections. To access the wiring terminal block, open

the cover of the H-335 by removing the four cover screws. Whenever tightening or loosening the cover

screws, turn each screw only a turn or two at a time. Try to equalize the stress on the lid. This is especially

important when the O-ring in the lid is near full compression.

Make certain the cable properly seals in the grommet of the liquid-tight cable fitting and that the O-ring in

the fitting is tight against the box. The connection must be water tight. Other grommet diameters and

fittings are available from the factory.

The H-335 has a removable 4-pin wiring terminal block for connecting the SDI-12 cable. Unplug the

terminal block and make the connections to the cable. The connections are labeled on the circuit board.

Check to make certain the connections are correct, then plug the terminal block into the H-335 circuit