Appendix

Measurements
Along a wall / other surface
The values in table 1 assume the ultrasonic
signal is sent along a smooth surface like
a wall or plane without any projections,
joints, butts etc.
If the surface is not smooth or has projec-
tions (i.e. joints on prefab elements), the
ultrasonic signal will be impedeaded too
much, and for that reason
the values for minimum distance to wall in
table 1 should be increased with
50 - 100 % !
Through a concrete deck
When the ultrasonic sensor is measuring
through a concrete deck, the dimension
of the opening should be made as shown
below: (See table 1 for the sensor spread.)

In a tank / container
If the ultrasonic sensor is mounted for
measurement of the level in a closed tank or
container, it should measure through a pipe
with a cutoff as shown below:

Through pipe for foam protection
When measuring on liquids prone to building
up foam on the surface, it is often necessary
to measure through a pipe, since the build
up of foam rarely will occur inside the pipe.

Measurement through a concrete deck with

45 - 60 ° edge cutoff.

Measurement through a concrete deck with

sharp edge.

30 - 45 °

Min. diameter (D) =
sensor spread + 100 %

Measurement through a pipe for foam protection.

Min. diameter (D)

= sensor spread +

100 %

Min. diameter (D) =

sensor spread

+ 50 %

Measurement in a closed container or tank.