Appendix – MJK Automation Shuttle Ultrasonic Level Transmitter and Sensor User Manual

Page 66

Advertising
background image

66

GB Shuttle Manual 100316

SW 838023

Appendix

Min. level for accept of ultrasonic echo
Enter the access code (see page

58

) and press 'Shift' + 'B':

If Shuttle

®

periodically has a system error and/or the level

readout jumps to a high or low level during measuring in fa-
vourable conditions, it may be necessary to increase the limit
for accept of the ultrasonic echo. (See also page

65

.)

On the contrary, it can be necessary to decrease the limit,
if it is difficult to get a good echo, e.g. long measuring dis-
tances on difficult surfaces.
Note:

Changes may affect the possible measuring range.

Use the arrow keys to select a new value:

Confirm the new setting:

The actual setting is shown immediately:
(Value in seconds.)

Shuttle

®

is ready for a new selection of a password protect-

ed menu after pressing 'Enter'.
(Re-entering the access code is not necessary if a menu
selection is made within 5 minutes.)

Press 'Escape' if no further password protected menu
selections are needed …

... or confirm with 'Enter' that the changes should be saved,
whereupon Shuttle

®

revert to normal read-out, and the next

password protected menu can be selected.
(Press 'Escape' if the changes should not be saved.)

Advertising