Modbus communication modules, Gnd b a gnd gnd rs485, B a gnd pe plc unit #1 – Xylem 205546 Modbus Communication Modules for Displays User Manual

Page 11

Advertising
background image

11

2.1.5 Connection Examples

2.1.5.1 One Connected Unit

This example illustrates connection, termination and ID configuration of a
single unit with a communication module and a PLC.

GND
B
A
GND

GND

RS485

Termination OFF

ON

GND GNDB

PCB no.: 510327-xxx
Communication RS485

3V3

5V5

5V
RTS

Rx

Tx

3V3

GND
B
A
GND

GND

RS485

Termination OFF

ON

B
A
GND

PE

PLC

Unit #1

Figure 3. One Connected Unit

Exampe ID settings
If the connected unit has ID=1 (seen from the com module), and the com
module has ID offset=200, the SRO Modbus ID is “201” (200 + 1, seen from
the PLC).

Termination
Modbus RS 485 communication requires bus termination. Therefore the con-
nected COM module’s termination dip switch is set in “ON” position.

2. Communication Modules

Modbus Communication Modules