EN 6.81 Modbus Communication Module 205546 Manual 1212

Register

address

Register

name

Type

Security

Read/

Write

Comments

637

Batch counter 2 - value

batch missing

F32 {low}

None

Read-only

638

See above

F32

{high}

-

-

Status I/O Bits

Register

address

Register name

Type

Security

Read/Write

1001

System error bit 1-16

B16

None

Read-only

Bits

System error bit { on = 1 & off = 0 } (to force zero write 12(0x0C) in address 5120 )

Bit 1 = Factory reset has occurred (some settings have changed)

Bit 2 = Eeprom write error (see log for details)

Bit 3 = Flow totalizer eeprom error (None-resetable counter may be invalid in Eprom)

Bit 4 = Sensor setting error (some settings are invalid or changed)

Bit 5 = Counter output Forward Pulsoverflow (too low puls volume)

Bit 6 = Counter output Reverse Pulsoverflow (too low puls volume)

Bit 7 = Batch1 counter overflow

Bit 8 = Batch2 counter overflow

Bit 9 = Flow totalizer overflow (none-resetable counter may be invalid in Eprom)

Bit 10-16 = Reserved and read-value is 0 (zero)

Register

address

Register name

Type

Security

Read/Write

1002

Alarm / sensor error

B16

None

Read-only

Bits

Status bit resetable { On = 1 & Off = 0 }

Bit 1 = empty pipe (see settings for possible enable / disable and on delay)

Bit 2 = low flow (see settings for possible enable / disable and on delay)

Bit 3 = high flow (see settings for possible enable / disable and on delay)

Bit 4 = mA flow error (flow is over or under possibel output)

Bit 5 = output coil error (see settings for possible enable / disable and on delay)

Bit 6 = sensor error (see settings for possible enable / disable and on delay)

Bit 7 = mA out not connected (see settings for possible enable / disable and on delay)

Bit 8 = Input over range error (see settings for possible enable / disable and on delay)

Bits 9-16 = Reserved and read-value is 0 (zero)

Register

address

Register name

Type

Security

Read/Write

1003

Status bits (Part 1)

B16

None

Read-only

Bits

Bit 1 = batch counter 1 - batch is ended = 1 / running = 0

Bit 2 = batch counter 2 - batch is ended = 1 / running = 0

Bit 3 = batch counter 1 - too big adaptive batch error = 1 / no error = 0

Bit 4 = batch counter 2 - too big adaptive batch error = 1 / no error = 0

Bits 5-16 = reserved