Data Transmitter 795

SW ver. 830434

6

Programming of main functions

6.1

Select language

Select the desired language with the arrow keys
and confirm with ENTER.

6.2

Set time and date

Enter time and date with the numerical keys or
the arrow keys. Confirm with ENTER:

Just press ENTER at all entries if changes are not
needed in order to proceed to the next menu.

6.3

Automatic change between summer
time and winter time

Select if the clock should change automatically
between summer time and winter time:

Use the arrow keys to select and confirm with
ENTER.

Just press ENTER at all entries if changes are not
needed in order to proceed to the next menu:

6.4

Access code enabled/disabled

Select if an access code is required to gain ac-
cess to the remaining system menus. This
function make it possible to protect the system
configuration from unauthorized changes:

Use the arrow keys to select and confirm with
ENTER.

6.4.1 Enter password

If access code protection is selected, a 4-digit
access code is required in order to gain access
to the remaining system menus.

6.5

Calculation of average values on
analogue inputs

The value of an analogue input is recorded every
second, and every 5 minutes the values is log-
ged. If averaging of the analogue values are
selected, an average of the analogue value over
the last 5 minutes will be calculated and logged.

If averaging is not selected, the analogue value at
the actual time will be logged.

Use the arrow keys to select and confirm with
ENTER.

6.6

Data logging interval

The data logging interval is used for the extended
logging function, where the value for the analogue
input and the level from MJK Pump Controller
704 is stored.

The interval between loggings can be chosen
amongst the following values: 30 sec. (00:30), 1
min. (01:00), 5 min. (05:00), 10 min. (10:00), 30
min. (30:00) and 1 hour (60:00).

Use the arrow keys to select and confirm with
ENTER.

6.7

Tone / pulse dialing

Select between pulse or tone dialing from a
telephone modem:

Use the arrow keys to select and confirm with
ENTER.

6.8

Alarm call on power failure

If alarm call at power failure is selected, the Data
Transmitter will call the first telephone number in
the telephone list when the power supply fail. A
power failure will not be detected before the
supply has been gone for minimum 30 sec.
Hereby alarm calls on short power surges are
avoided.

Use the arrow keys to select and confirm with
ENTER.