General setup parameters, Location in register list – Xylem CHATTER RTU and E-mail User Manual

Page 188

Advertising
background image

USERS MANUAL

CHATTER™ DATA LOGGER

188

General setup parameters

Name

Reg
#

Modbus
R/W

Typ
e

FW

Description

Station ID

2

R/W 3/16 U16

Used for ID device in SCADA system (not used
internally in device) Default is 0, not in use

RTU Name/ID Tag

7

R/W 3/16 STR

20

RTU Name / Location Name Default = "Chatter1" ( 1
Depends on Device ID)

Last Battery measurement

18

R 3

U16

Last battery measurement after use of modem for
last call [mV]

0 = Unknown / not updated yet
< 3000mV = Replace battery
3500 - 3700mV = OK, but this value is depending
on how long the last connection was.

MJK Serial No

28

R 3

U32

MJK serial no. identifying Chatter™ Data Logger
when contacting MJK

GSM signal-strength

30

R 3

U16

0-31 (99 = Unknown or not ready yet)

Second

40

R/W 3/16 U16

ex 59 = 59sec (sec .. to year must be written in one
telegram)

Minute

41

R/W 3/16 U16

Hour

42

R/W 3/16 U16

Day

43

R/W 3/16 U16

Month

44

R/W 3/16 U16

Year

45

R/W 3/16 U16

Modem Online Time left

46

R/W 3/16 U16 85000

7

Modem time left for call at this time [sec] Restarted
daily.
If 0, the Chatter™ Data Logger is not allowed to
make any calls before next daily reset