3.1

PREPARATION

3.1.1 After package is installed and foundation bolts

are tightened, check pump alignment. Refer to

specific pump Installation, Operation & Mainten-

ance manual for alignment procedures.

3.1.2 On packages with enclosures, inspect doors for

proper alignment. Doors may become misaligned

during shipping, handling and/or installation.

Realign doors to provide and even 1/8" clearance

between door and frame.

3.1.3 Inspect all piping connections. Some joints may

have been loosened and not retightened after

completion of factory hydrotest to facilitate sys-

tem drainage. Joints may also become loose dur-

ing transit due to vibration and shock. All joints

are to be checked for tightness. Flanged joints

should be checked for proper torque of all flange

bolts prior to filling the system with fluid.

3.1.4 Before starting all pumps and drivers should be

checked for proper lubrication.

3.1.5 Piping should be clean and flushed prior to

operation.

3.1.6 Refer to specific electrical and mechanical equip-

ment manuals for start up instructions.

3.1.7 On electric driven units check all connections to

motors and starting devices with wiring diagram.

3.1.8 On diesel driven units check all connections

between engine terminal block and control panel.

3.1.9 On diesel driven units, prior to filling the fuel tank,

inspect fuel line piping connections. Joints may

become loose during transit due to vibration and

shock. All joints are to be checked for tightness.

After filling the fuel tank, inspect the fuel line for

leaks. Tighten any joints as required.

3.1.10 Prior to start up, ensure valve to hose header and

valves on outside of hose header are closed.

3.2

START-UP

3.2.1 The following procedure is suggested for initial

start-up.

3.2.2 Fill the system with fluid.

3.2.3 Vent all the high points in the piping system to

remove trapped air. Threaded connections are

supplied on bypass loops, flow meter loops and

pressure sensing lines for venting.

CAUTION: Failure to maintain a proper clear-

ance will cause an interference and/or hardware

misalignment. FAILURE TO FOLLOW THESE

INSTRUCTIONS COULD RESULT IN PROPERTY

DAMAGE AND/OR MODERATE PERSONAL

INJURY.

CAUTION: Failure to check all joints for tight-

ness and flange bolts for proper torque could

result in leaks and/or flooding. FAILURE TO FOL-

LOW THESE INSTRUCTIONS COULD RESULT IN

PROPERTY DAMAGE AND/OR MODERATE PER-

SONAL INJURY.

CAUTION: Failure to check all joints could

result in leaks and/or environmental hazard.

FAILURE TO FOLLOW THESE INSTRUCTIONS

COULD RESULT IN PROPERTY DAMAGE AND/OR

MODERATE PERSONAL INJURY.

CAUTION: Stuffing Box Damage may occur. Do

not run pumps dry. Fill and vent the pump volute

prior to operation. FAILURE TO FOLLOW THESE

INSTRUCTIONS COULD RESULT IN PROPERTY

DAMAGE AND/OR MODERATE PERSONAL

INJURY.

DANGER: High voltage 3 phase power can kill.

Disconnect and lockout power prior to servicing

unit. FAILURE TO FOLLOW THESE INSTRUCTIONS

WILL RESULT IN SERIOUS PERSONAL INJURY,

DEATH, AND/OR PROPERTY DAMAGE.