APPENDIX B

ELECTRICAL WIRING AND CONTROL SETTINGS – FINAL CHECK LIST

___ 1. Does the feeder line voltage correspond to the

unit voltage? Check the unit nameplate or motor

terminal connection.

___ 2. Are the feeder wires correctly sized for the load?

___ 3. Is the unit properly grounded?

___ 4. Have all the power terminals in the control panel

been checked for tightness? This is imperative

since stranded wires tend to "flow" and become

loose after initial installation.

WARNING: Electrical shock hazard. Inspect all

electrical connections prior to powering the

unit. Wiring connections must be made by a qualified

electrician in accordance with all applicable codes,

ordinances, and good practices. FAILURE TO FOL-

LOW THESE INSTRUCTIONS COULD RESULT IN

SERIOUS PERSONAL INJURY, DEATH, AND/OR

PROPERTY DAMAGE.

WARNING: Conduit grounds are not adequate.

A separate ground wire must be attached to the

ground lug provided in the enclosure to avoid poten-

tial safety hazards. FAILURE TO FOLLOW THESE

INSTRUCTIONS COULD RESULT IN SERIOUS

PERSONAL INJURY, DEATH, AND/OR PROPERTY

DAMAGE.

DANGER: High voltage 3 phase power can kill.

Disconnect and lock out power prior to servic-

ing unit. FAILURE TO FOLLOW THESE INSTRUC-

TIONS WILL RESULT IN SERIOUS PERSONAL

INJURY, DEATH, AND/OR PROPERTY DAMAGE.