Installation and operation manual moh2, Technical data – Xylem MOH2 Multi zone mixing module (obsolete) User Manual

Page 16

Advertising
background image

16

Installation and operation manual MOH2

www.lainginc.com

Technical data

Maximum system pressure

145 PSI (10 bar )

Circulator

see diagram

Floor heating loop
Maximum temperature

140°F (60°C)

Feed connection

1" female thread/flange for segmented
plastic manifold

Return connection...

Boiler loop
Maximum temperature

220°F (105°C)

Feed connection

3/4" female thread in ball valve

Return connection...

Heating performance of MOH2 module
• The heating performance of the MOH2 module is dependent on

- Hydraulic characteristic of the floor heating system
- Differential pressure between boiler feed and return
- Temperature difference between boiler loop and floor heating loop

• Example

- Floor heating feed temperature 50°C [120°F]
- Floor heating return temperature 42°C [108°F]
- Pressure drop in floor heating loops including manifolds 23 kPa [7.5ft]
- The pump curve yields for this differential pressure a flow rate of the

integrated circulator of 1.7 m

3

/h [7.48 US GPM].

- This means that the MOH2 module can distribute 15.8 kW. in the

floor heating system.

- With an assumed delta T in the boiler loop of 25 K. [45°F], the boiler

loop needs to furnish 0.5 m

3

/h [2.2 US GPM] at peak heat demand

- Since the boiler return temperature is equal to or larger than the

floor heating return temperature, the minimum boiler feed temperature
at peak heat demand is 67°C [150°F]

- The diagram for the presetting knob which adjusts the boiler side

differential pressure shows that for this flow rate, the differential
pressure in the boiler loop needs to be at least 20 kPa [6.6 ft].