Installation and operation manual moh2, Changing out the circulator – Xylem MOH2 Multi zone mixing module (obsolete) User Manual

Page 19

Advertising
background image

19

Installation and operation manual MOH2

www.lainginc.com

Changing out the circulator

Preparation
Caution: only a properly licensed electrician should disconnect and

reconnect the circulator.

• Remove electrical power even if you only want to clean the circulator

and not remove it.

• Close the ball valves 10 and 11 on the boiler feed and return side
• Connect the drain hose to the lower drain valve 13. In this way, the

check valve 7 will close automatically and the manifold will not drain
completely.

• Make sure that the drain hose can drain below the level of the circulator

pump

Draining of the water
• Open the drain valve 13
• When all water has drained, loosen the upper pump mounting screw to

allow air entry.

• Drain an additional 1/4 liter.
• Now the water should be below the level of the pump
Changing the circulator
• Remove both pump mounting screws.
• Take care when removing the pump since the rotor is only sitting loosely

on the ceramic ball and can fall out. Tilt the wiring end downward slightly
to prevent this.

• After removing the drive unit you can remove the rotor and clean it if

necessary.

• If the rotor have scratches in the lower part, the bearing has run out and

a new drive unit needs to be installed

• Have a properly licensed electrician disconnect the old circulator and

reconnect a new one.

• Before reassembly, carefully clean the seal ring and the housing.
• Reinsert the drive unit and tighten the two pump mounting screws
Restarting the system
• Refill unit by connecting the drain hose to a faucet. The air will bleed

through the automatic air purger.

• Open the valves on the boiler feed and return side
• Re-energize the unit
• The unit should be ready for operation