2 lifting, 3 mounting, 4 tightening torques – Bell & Gossett P2001487 Technologic Pump Controller User Manual

Page 12

Advertising
background image

Illustration 2.1 Top and Bottom Cooling Clearance

Enclosure

A2-A5

B1-B4

C1, C3

C2, C4

a/b [mm]

100

200

200

225

Table 2.1 Minimum Airflow Clearance Requirements

2.3.2 Lifting

•

Check the weight of the unit to determine a safe
lifting method

•

Ensure that the lifting device is suitable for the
task

•

If necessary, plan for a hoist, crane, or forklift with
the appropriate rating to move the unit

•

For lifting, use hoist rings on the unit, when
provided

2.3.3 Mounting

•

Mount the unit vertically

•

The frequency converter allows side by side
installation

•

Ensure that the strength of the mounting location
will support the unit weight

•

Mount the unit to a solid flat surface or to the
optional back plate to provide cooling airflow
(see Illustration 2.2 and Illustration 2.3)

•

Improper mounting can result in over heating
and reduced performance

•

Use the slotted mounting holes on the unit for
wall mounting, when provided

Illustration 2.2 Proper Mounting with Back Plate

Item A in Illustration 2.2 and Illustration 2.3 is a back plate
properly installed for required airflow to cool the unit.

Illustration 2.3 Proper Mounting with Railings

Item

#

Description

1

Back plate

Table 2.2 Legend to Illustration 2.3

NOTE

Back plate is needed when mounted on railings.

2.3.4 Tightening Torques

See 10.4 Connection Tightening Torques for proper
tightening specifications.

Installation

9