3 fuse specifications, 1 branch circuit protection fuses – Bell & Gossett P2001487 Technologic Pump Controller User Manual
Page 84

10.3 Fuse
Specifications
10.3.1 Branch Circuit Protection Fuses
For compliance with IEC/EN 61800-5-1 electrical standards the following fuses are recommended.
Frequency
converter
Maximum fuse size
Voltage
Type
200-240 V - T2
1K1-1K5
16A
1
200-240
type gG
2K2
25A
1
200-240
type gG
3K0
25A
1
200-240
type gG
3K7
35A
1
200-240
type gG
5K5
50A
1
200-240
type gG
7K5
63A
1
200-240
type gG
11K
63A
1
200-240
type gG
15K
80A
1
200-240
type gG
18K5
125A
1
200-240
type gG
22K
125A
1
200-240
type gG
30K
160A
1
200-240
type gG
37K
200A
1
200-240
type aR
45K
250A
1
200-240
type aR
380-480 V - T4
1K1-1K5
10A
1
380-500
type gG
2K2-3K0
16A
1
380-500
type gG
4K0-5K5
25A
1
380-500
type gG
7K5
35A
1
380-500
type gG
11K-15K
63A
1
380-500
type gG
18K
63A
1
380-500
type gG
22K
63A
1
380-500
type gG
30K
80A
1
380-500
type gG
37K
100A
1
380-500
type gG
45K
125A
1
380-500
type gG
55K
160A
1
380-500
type gG
75K
250A
1
380-500
type aR
90K
250A
1
380-500
type aR
1) Max. fuses - see national/international regulations for selecting an applicable fuse size.
Table 10.14 EN50178 fuses 200 V to 480 V
Specifications
81
10
10