Inspect for

Description

☑

Environmental consider-

ations

•

See equipment label for the maximum ambient operating temperature limits

•

Humidity levels must be 5-95% non-condensing

Fusing and circuit

breakers

•

Check for proper fusing or circuit breakers

•

Check that all fuses are inserted firmly and in operational condition and that all circuit breakers are

in the open position

Earthing (Grounding)

•

The unit requires an earth wire (ground wire) from its chassis to the building earth (ground)

•

Check for good earth connections (ground connections) that are tight and free of oxidation

•

Earthing (grounding) to conduit or mounting the back panel to a metal surface is not a suitable

earth (ground)

Input and output power

wiring

•

Check for loose connections

•

Check that motor and mains are in separate conduit or separated screened cables

Panel interior

•

Inspect that the unit interior is free of dirt, metal chips, moisture, and corrosion

Switches

•

Ensure that all switch and disconnect settings are in the proper positions

Vibration

•

Check that the unit is mounted solidly or that shock mounts are used, as necessary

•

Check for an unusual amount of vibration

Table 3.1 Start Up Check List