Bell & Gossett P2002379A Duty-Standby Pumps Alternation User Manual
Page 7

Parameters number
Description
Set to Setup 3
Set to Setup 4
Comments
5–31
Terminal 29
Digital Output
[160] No alarm
[168] Hand / Off
Output is high when there
is no alarm, in Off and
Hand on mode, and Timer
0 expires or [OK] and [>]
keys are pressed in Setup
4.
Output is low when alarm
has occurred, and Timer 0
expires or [OK] and [>]
keys are pressed in Setup
3.
Relays
5–40.0
Function Relay
[9] Alarm
[9] Alarm
Default setting
5–40.1
Function Relay
[5] Running
[5] Running
Default setting
Smart Logic
13–00
SL Control Mode
[1] On
[1] On
Enables the Smart Logic
Controller
13–01
Start Event
[1] True
[1] True
Enters the fixed value of
TRUE in the logic rule.
13–02
Stop Event
[0] False
[0] False
Enters the fixed value of
FALSE in the logic rule.
Timers
13–20.0
SL Controller Timer
24:00:00.000
24:00:00.000
Timing between
alternations set by Timer 0.
13–20.1
SL Controller Timer
00:00:02.000
00:00:02.000
Timing for pressing [OK]
and [>] keys set by Timer
1.
Logic Rules 0
13–40.0
Logic Rule
Boolean 1
[43] OK Key
[43] OK Key
Drives can be alternated by
pressing [OK] and [>] keys
at the same time ot the
Timer 0 expires.
13–41.0
Logic Rule
Operator 1
[1] AND
[1] AND
13–42.0
Logic Rule
Boolean 2
[46] Right Key
[46] Right Key
13–43.0
Logic Rule
Operator 2
[2] OR
[2] OR
13–44.0
Logic Rule
Boolean 3
[30] SL Time-out 0
[30] SL Time-out 0
Logic Rules 1
13–40.1
Logic Rule
Boolean 1
[37] Digital Input DI32
[37] Digital Input DI32
Output is high when the
output from Slave drive is
low or [OK] and [>] keys
are pressed or Timer 0
expires.
13–41.1
Logic Rule
Operator 1
[6] NOT OR
[6] NOT OR
13–42.1
Logic Rule
Boolean 2
[26] Logic rule 0
[26] Logic rule 0
13–43.1
Logic Rule
Operator 2
[0] DISABLE
[0] DISABLE
13–44.1
Logic Rule
Boolean 3
[0] False
[0] False
Operation
Duty-Standby Pumps Alternation INSTRUCTION MANUAL
5