Bell & Gossett P2002379A Duty-Standby Pumps Alternation User Manual

Page 8

Advertising
background image

Parameters number

Description

Set to Setup 3

Set to Setup 4

Comments

Logic Rules 2
13–40.2

Logic Rule
Boolean 1

[37] Digital Input DI32

[37] Digital input DI32

Output is high when input

from Slave drive is high

and [OK] and [>] keys are

pressed or Time 0 expires.

13–41.2

Logic Rule
Operator 1

[1] AND

[1] AND

13–42.2

Logic Rule
Boolean 2

[26] Logic rule 0

[26] Logic rule 0

13–43.2

Logic Rule
Operator 2

[0] DISABLE

[0] DISABLE

13–44.2

Logic Rule
Boolean 3

[0] False

[0] False

State 1
13–51.0

SL Controller Event

[1] True

[1] True

Start at Setup 3

13–52.0

SL Controller Action

[4] Select set-up 3

[4] Select set-up 3

State 2
13–51.1

SL Controller Event

[1] True

[1] True

If [OK] and [>] keys are

pressed, switch

debouncing timer prevents

unexpected results

occurred.

13–52.1

SL Controller Action

[30] Start time 1

[30] Start timer 1

State 3
13–51.2

SL Controller Event

[31] SL Time-out 1

[31] SL Time-out 1

After the switch

debouncing timer expires,

the alternation timer 0 is

reset.

13–52.2

SL Controller Action

[29] Start timer 0

[29] Start timer 0

State 4
13.51.3

SL Controller Event

[28] Logic rule 2

[28] Logic rule 2

If digital input from Slave is

high and output from logic

rule 0 is high, select Setup

4.

13.52.3

SL Controller Action

[5] Select set-up 4

[4] Select set-up 4

State 5
13–51.4

SL Controller Event

[1] True

[1] True

If [OK] and [>] keys are

pressed, switch

debouncing timer prevents

unexpected results

occurred.

13–52.4

SL Controller Action

[30] Start timer 1

[30] Start timer 1

State 6
13–51.5

SL Controller Event

[31] SL Time-out 1

[31] SL Time-out 1

After the switch

debouncing timer expires,

the alternation timer 0

starts.

13–52.5

SL Controller Action

[29] Start timer 0

[29] Start timer 0

State 7
13–51.6

SL Controller Event

[27] Logic rule 1

[27] Logic rule 1

If logic Rule 1 is high, no

action.

13–52.6

SL Controller Action

[1] No Action

[1] No Action

Table 2: SLAVE Duty-Standby Parameters

Parameters Number

Description

Set to Setup 3

Set to Setup 4

Comments

Operation / Display

Operation

6

Duty-Standby Pumps Alternation INSTRUCTION MANUAL

Advertising