Bell & Gossett P2002379A Duty-Standby Pumps Alternation User Manual
Page 9

Parameters Number
Description
Set to Setup 3
Set to Setup 4
Comments
0–01
Language
[0] English
[0] English
English language is
selected.
0–03
Regional Settings
[1] North America
[1] North America
Sets 1–20 Motor Power
[HP] to HP and the default
value of 1–23 Motor
Frequency to 60 Hz.
0–10
Active set-up
[9] Multi Set-up
[9] Multi Set-up
Uses the setting from 0–12
This Set-up Linked to.
0–11
Programming Set-up
[9] Active Set-up
[9] Active Set-up
0–12
This Set-up Linked to
[0] Not linked
[3] Set-up 3
Enable conflict-free
changes between Set-up 3
and Set-up 4.
Note: Also set Setup 1 and
Setup 2 to Set-up 3.
0–37
Display Text 1
Lead Pump
Lead Pump
This message indicates the
running pump.
0–38
Display Text 2
Lag Pump
Lag Pump
This message indicates the
pump is waiting for
alternation.
Digital In/Out
5–01
Terminal 27 Mode
[0] Input
[0] Input
This digital input is not
used.
5–02
Terminal 29 Mode
[1] Output
[1] Output
This digital input provides
output to the Slave drive.
5–10
Terminal 18
Digital Input
[8] Start
[0] No operation
The slave drive can only
start in Set-up 3.
5–11
Terminal 19
Digital Input
[24] Set-up select
Bit 1
[24] Set-up select
Bit 1
This digital input is tied to
+24 V DC as input high for
the most significant bit of
Set-up 3 and Set-up 4.
Note: Also set Setup 1 and
Setup 2 to this value (Set-
up select bit 1)
5–12
Terminal 27
Digital Input
[0] No Operation
[0] No Operation
Terminal 27 is not used.
5–14
Terminal 32
Digital Input
[23] Set-up select
bit 0
[23] Set-up select
bit 0
NOTE: Also Setup 1 and
Setup 2 to this value (Set-
up select bit 0)
5–31
Terminal 29
Digital Output
[70] Logic rule 0
[70] Logic rule 0
Output is low when alarm
has occurred or in Off or
Han on mode
Relays
5–40.0
Function Relay
[9] Alarm
[9] Alarms
Default setting
5–40.1
Function Relay
[5] Running
[5] Running
Default setting
Smart Logic
13–00
SL Control Mode
[0] Off
[0] Off
Disables the Smart Logic
Controller
Comparator 0
13–10.0
Comparator Operand
[180] Local reference active [180] Local reference active Uses for comparing with
the Off mode.
13–11.0
Comparator Operand
[5] TRUE longer than...
[5] TRUE longer than...
Logic Rules 0
Operation
Duty-Standby Pumps Alternation INSTRUCTION MANUAL
7