Parameter values – Bell & Gossett P2002379A Duty-Standby Pumps Alternation User Manual
Page 6

Parameter values
Table 1: MASTER Duty-Standby Parameters
Parameters number
Description
Set to Setup 3
Set to Setup 4
Comments
Operation / Display
0–01
Language
[0] English
[0] English
English language is
detected
0–03
Regional settings
[1] North America
[1] North America
Sets 1–20 Motor Power
[HP] to HP and the default
value of 1–23 Motor
Frequency to 60 Hz
0–10
Active Set-up
[9] Multi Set-up
[9] Multi Set-up
Uses the setting from
0–12 This Set-up Linked to.
0–11
Programing Set-up
[9] Active Set-up
[9] Active Set-up
The set-up in which the
frequency converter is
operating.
0–12
The Set-up Linked to
[0] Not linked
[3] Set-up 3
Enable conflict-free
changes between Set-up 3
and Set-up 4.
Note: Also set Setup 1 and
Setup 2 to Set-up 3.
0–37
Display Text 1
Lead Pump
Lead Pump
This message indicates the
running pump.
0–38
Display Text 2
Lag Pump
Lag Pump
This message indicates the
pump that is waiting for
alternation.
Digital In/Out
5–01
Terminal 27 Mode
[0] Input
[0] Input
This digital input is not
used.
5–02
Terminal 29 Mode
[1] Output
[1] Output
This digital input provides
output to the Slave drive.
5–10
Terminal 18 Digital Input
[8] Start
[0] No Operation
The Master drive can only
start in Set-up 3.
5–11
Terminal 19 Digital Input
[24] Set-up select bit 1
[24] Set-up select bit 1
This digital input is tied to
+24 V DC as input high for
the most significant bit of
Set-up 3 and Set-up 4.
Notes: Also set Setup 1 and
Setup 2 to this value (Set-
up select bit 1).
5–12
Terminal 27 Digital Input
[0] No Operation
[0] No Operation
This digital input is not
used.
5–14
Terminal 32 Digital Input
[23] Set-up select bit 0
[23] Set-up select bit 0
This digital input provides
the least significant bit
value in selecting Set-up 3
or Set-up 4.
Notes: Also set Setup 1 and
Setup 2 to this value (Set-
up select bit 0)
Operation
4