Commercial Water

Goulds Water Technology

INSTALLATION PROCEDURES

2.1.7 Foundation must be flat and substantial to eliminate strain when tightening bolts.

Use rubber mounts to minimize noise and vibration.

2.1.8 Tighten motor hold down bolts before connecting piping to plumbing.

3.0 SUCTION PIPING

3.1 Low static suction lift and short, direct suction piping is desired. For suction lift over 10 feet and liquid

temperatures over 120º F, consult pump performance curve for Net Positive Suction Head required.

3.2 Suction pipe must be at least as large as the suction connection of the pump. Smaller size will degrade
performance.

3.3 If larger pipe is required, an eccentric pipe reducer (with straight side up) must be installed at the pump.

3.4 Installation with pump below source of supply

3.4.1 Install full flow isolation valve in piping for inspection and maintenance.

DO NOT USE SUCTION ISOLATION VALVE TO THROTTLE PUMP.

3.5 Installation with pump above source of supply

3.5.1 Avoid air pockets. No part of piping should be higher than pump suction connection. Slope piping

upward from liquid source.

3.5.2 All joints must be airtight.

3.5.3 Foot valve to be used only if necessary for priming or to hold prime on intermittent service.

3.5.4 Suction strainer open area must be at least triple the pipe area.

3.6 Size of inlet from liquid source and minimum submergence over inlet, must be sufficient to prevent air

entering pump through vortexing. See Figures 1-4.

CAUTION

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

H

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

V

H

=

Min.

Submer

gence

in

feet

V = Velocity in feet per second

=GPM x 0.321 GPM x 0.4085

Area D

2

1.5D

min.

3.0D

min.

D

D

H min.

D

min.

2

---------

---------

D

H min.

D

H min.

---------

---------

Figure 1

Figure 2

Figure 3

Figure 4