For the 24v burner/24v feeder setups – Xylem MM 201H Series 67 and 767 Low Water Cut-Offs For Steam Boilers User Manual

Page 11

Advertising
background image

For the 24V Burner/24V Feeder setups.

BURNER

101A-24

120 VAC
SUPPLY

24V TRANSFORMER
(101-24V-48)

1

2

3

4

N

H

24V

69

c. Connect the "hot" wire from the boiler trans-

former to terminal #2 of the low water cut-off.
Connect the "hot" side of the water feeder
transformer to terminal #3 of the low water
cut-off. Connect the neutral side of the boiler
transformer to the burner. Using a wire nut,
connect the neutral side of the water feeder
transformer to the water feeder.

BURNER

101A-24

120 VAC
SUPPLY

24V TRANSFORMER
(101-24V-48)

1

2

3

4

N

H

24V

d. Connect the wire from the burner to terminal

#1 of the low water cut-off. Connect a wire
from terminal #4 of the low water cut-off to the
remaining wire in the water feeder. Wire nut
together.

BURNER

101A

120 VAC
SUPPLY

N

H

24V

1

2

3

4

69

Wiring Alternative

For the 120V Burner/24V Feeder setups.

For the 24V Burner/120V Feeder setups.

BURNER

101A-24

120 VAC
SUPPLY

24V TRANSFORMER
(101-24V-48)

TO AVOID DAMAGE TO 101A
SOLENOID COIL, TRANSFORMER
101-24V-48 MUST BE USED.

N

H

1

2

3

4

69

11

IMPORTANT: It is very important that you use the transformer supplied with the 101-A-24. The boiler

transformer in most cases is not big enough to handle the current draw of the 101-A-24.
Use the supplied transformer (101-24-48). In most cases it will handle both the boiler
and feeder. Do not try to use two transformers in the same circuit.