Troubleshooting, Diagram 1 diagram 2, Diagram 3 diagram 4 – Xylem MM 214E Series 61 Low Water Cut-Off User Manual

Page 6

Advertising
background image

6

0

2

0

4

1

0

3

0

0

2

0

4

1

0

3

0

0

2

0

4

1

0

3

0

SCHEMATIC OF TWIN SWITCH

INTERNAL OPERATION

NORMAL WATER LEVEL

FEEDER OR ALARM
OPERATING LEVEL

LOW WATER CUT-OFF
OPERATING LEVEL

NEUTRAL WIRE

NEUTRAL WIRE

HOT WIRE

HOT WIRE

TO BURNER

TO ALARM

SAFETY
SWITCH

0

2

0

4

1

0

3

0

USED AS MAIN LINE SWITCH

Diagram 1

Diagram 2

TO LINE

TO BURNER

STARTER

NO. 11
SWITCH

L1
L2
L3

0

2

0

4

1

0

3

0

USED AS PILOT SWITCH IN SERIES WITH

HOLDING COIL OF AUTOMATIC STARTER

NEUTRAL WIRE

TO

TWO WIRES OF 101A

OR TO ALARM CIRCUIT

HOT WIRE

TO BURNER

JUMPER

NO. 11
SWITCH

0

2

0

4

1

0

3

0

USED WITH MODEL 101 ELECTRIC

WATER VALVE OR IN ALARM CIRCUIT

Diagram 3

Diagram 4

IMPORTANT: Low water cut-off circuit of the 61 series must be electrically wired in series with all other boiler
limit operating controls.

TROUBLESHOOTING

Problem:

1. Burner does not shut off on low water.

a. Cause: Float chamber is loaded with mud or

sediment.

Test: With water level below the control

check if terminals 1 and 2 are open. If
not, remove switch and manually test if
terminals 1 and 2 can be opened.

Solution: Open float chamber and clean. At this

time, check for a build-up of scale or
sediment between corrugations of the
bellows.

b. Cause: Contacts are fused together.

Test: Remove switch and operate manually to

verify proper switch operation.

Solution: Replace switch. Check electrical load

and make sure it is within the ratings of
the switch.

2. Electric water feeder does not shut off.

a. Cause: Build-up of scale or sediment between

corrugations of the bellows.

Test: With water level above the control,

check if terminals 3 and 4 are open. If
not, remove switch and manually test
to verify terminals 3 and 4 can be
opened.

Solution: Open float chamber and replace or

clean the bellows.

b. Cause: Contacts are fused together.

Test: Remove switch and operate manually

to verify proper switch operation.

Solution: Replace switch. Check electrical load

and make sure it is within the ratings of
the switch.