Step 2 - installing the remote sensor – Xylem MM 273E Model 750-HW-MT-120 Probe Type High Water Manual Reset Control Unit User Manual

Page 4

Advertising
background image

4

1/4" MIN. (6.4 mm)

1/4" MIN. (6.4 mm)

B

B

M

c. Insert the remote sensor (B) into the boiler

tapping (M) as determined in Step 1.

N

B

P

d. Using a wrench (N), tighten the brass hex

adapter (P) on the remote sensor (B) to
approximately 63 ft•lb (85 N•m). DO NOT
TIGHTEN BY TURNING THE SENSOR
HOUSING.

L

OR

L

b. Apply a small amount of pipe dope to the first

threads (L) of the remote sensor.

For All Remote Sensors

IMPORTANT: Do not use PTFE tape or thread
sealant.

B

A

a. Cut the probe (purchased separately) to desired length.

Screw, clockwise, the threaded stainless steel probe
extension (A) into the remote sensor (B). Carefully tighten
the locking nut to approximately 1 ft•lb (1.7 N•m). Do not
cut the clear plastic protective tube.

STEP 2 - Installing the Remote Sensor

For the Model RS-1-BR-1 sensors, only: