Determine where to install the remote sensor (sold separately) based on the following requirements:

Option A
a.
The Remote Sensor can be installed directly in a 1"

or larger tapping in the top of the boiler.

b. The probe of the RS-1-BR-1 Remote Sensor will

need to be cut to appropriate length based upon the
level where high water cutoff/alarm is desired.

c. The probe of the RS-1-LP Remote Sensor is

approximately 2" long therefore high water
cutoff/alarm will occur at that level.

d. There must be a minimum 1/4" (6.4mm) clearance

between the probe and any grounding surface inside
the boiler or pipe.

Option B
a.
The Remote Sensor can be installed directly into the

1" fittings of the boiler’s equalizing piping.

b. If installed in the upright or vertical position:

• The probe of the RS-1-BR-1 Remote Sensor will

need to be cut to appropriate length based upon
the level where high water cutoff/alarm is desired.

• The probe of the RS-1-LP Remote Sensor is

approximately 2" long therefore high water
cutoff/alarm will occur at that level.

c. If installed in the sideways or horizontal position:

• The probe of the RS-1-BR-1 Remote Sensor

cannot exceed 4" in length.

NOTE: The Remote Sensors SHOULD NOT be
installed in equalizing piping that is smaller than
1" NPT.

d. There must be a minimum 1/4" (6.4mm) clearance

between the probe and any grounding surface
inside the boiler or pipe.

STEP 1 - Where to Install the Remote Sensors

3

or

or

or

Upright or Vertical

Position

Sideways or Horziontal

Position