6

Wiring Diagram Legends

1. Bold lines indicate action to be taken in Step shown.

2. Dotted black lines indicate internal wiring.

PROBE

1

2

3

4

5

WHITE

NEUTRAL

HOT

Limit Circuit

ALARM

Note:

Contact positions shown

with water off probe

Remote Sensor Wiring:
• Connect wire from probe end to Terminal
• Connect wire from remote sensor green ground

screw to

Control Wiring:
• Connect 120V hot wire to terminal 1
• Connect 120V neutral wire to terminal 2
• Connect jumper wire from Terminal 1 to

Terminal 3

• Connect wire from beginning of limit circuit

(thermostat, gas valve, limits, etc.) to terminal 5

• Connect wire from end of limit circuit to terminal 2

N

P

M

b. For all wire connections to the terminal block (M).

1. Strip about 1/3" (8.5 mm) of insulation from

the wire.

2. Loosen the terminal screw (N), DO NOT

REMOVE, and move the wire clamping plate
(P) back until the plate touches the back side
of the screw head.

3. Insert the stripped end of the wire under the

wire clamping plate (P) and securely tighten
the terminal screw (N).

RS1-BR-1
SENSOR

• Install electrical conduit between Probe

Housing and Control Box.

Refer to and follow local codes and standards
when selecting conduit and electrical fittings.
Wires from Probe Housing and Control Box must
be in their own conduit. If they are run in conduit
with other wires, there may be interference that
can affect the performance of the control.

NOTE

Wire must be 18 AWG stranded with glass braided
silicone jacket (UL 3071) suitable for high
temperature (200˚C) service.

NOTE

connection "PROBE" on PCB.

Terminal connection "GND" on PCB.

GND