Installation, Step 1 - paddle sizing – Xylem MM 601H Series FS4-3 General Purpose Liquid Flow Switch User Manual

Page 4

Advertising
background image

4

Pipe

Flow

No-Flow

Size NPT

Maximum

Maximum

in. (mm)

Adjustment

Adjustment

2

(50)

69.2

50.3

3

(80)

162.5

143.5

4 (100)

276.0

241.0

5 (125)

550.0

440.0

6 (150)

977.0

728.0

Series FS4-3 “K” Factor

b. If the flow rate in the pipe exceeds the

maximum adjustment on the Flow Switch
use the following formula to change the
paddle length.

Paddle Length =

K

_______________

Flow Rate (GPM)

NOTE: If trimming the paddle for a no-flow action make sure
there is enough flow to activate switch.

a. If the paddle must be trimmed, measure the paddle

from the center of the large hole (A) to the length
required. Using non-serrated tin snips, trim the end (B)
on a curve just like the paddle was originally cut.

STEP 1 - Paddle Sizing

1" (25mm)

2" (51mm)

3" (76mm)

6" (152mm)

Determine the correct paddle length for your installation from
the chart below.

NOTE:
• All models (except FS4-3RP) include 4 paddles.
• FS4-3RP includes 1" and 6" paddles only.

INSTALLATION –

Pipe Size

Paddle Trim to Length

(Standard Length)

in.

(mm)

in.

(mm)

in.

(mm)

1

(25)

1

(25)

N/A

1

1

/

4

(32)

2

(51)

1

1

/

4

(32)

1

1

/

2

(40)

2

(51)

1

1

/

2

(38)

2

(50)

2

(51)

1

5

/

8

(41)

2

1

/

2

(65)

3

(76)

2

1

/

4

(57)

3

(80)

3

(76)

2

5

/

8

(67)

4

(100)

6

(152)

3

5

/

8

(92)

6

(150)

6

(152)

5

5

/

8

(143)

8+

(200+)

6

(152)

N/A