Step 5 - testing – Xylem MM 601H Series FS4-3 General Purpose Liquid Flow Switch User Manual

Page 7

Advertising
background image

7

b. Electrical Conduit Connection
• Connect electric conduit to flow switch electrical enclosure.
• Follow accepted electrical practices when installing fittings and making connections.
• Refer to and follow local codes and standards when selecting the types of electrical fittings and conduit to

connect to flow switch.

c. Determine which switch action is required for the

flow switch.
• “Flow” means that the switch will close circuit

C.-N.O. and open circuit C.-N.C. when flow rate
is increased above setpoint of flow switch.

• “No Flow” means that the switch will open circuit

C.-N.O. and close circuit C.-N.C. when flow rate
is decreased below setpoint of flow switch.

a. Place cover on flow switch and turn on power. Initiate fluid

flow through the system. Observe the device being
activated by the flow switch to determine if device is
operating as required.

b. Turn off fluid flow to determine if device is operating

as required.

c. Repeat initiating and turning off fluid flow several times

to test flow switch and device for proper operation.
- If operating as required, put system into service.
- If not operating as required, Flow Switch may need

to be adjusted.

d. Based upon the mode of operation (“Flow” or “No-

Flow”) required, complete the appropriate steps to
connect wires to flow switch. Use a Phillip’s head
screwdriver to loosen and tighten switch terminal
screws when attaching wires.
For “Flow” Mode of Operation (Fig. 1)
If the flow switch will be used to actuate a signal,
alarm or other device when

flow occurs, connect

the wire from that device to the “N.O.” contact.
Connect the “Hot” power supply wire to “C” terminal.
For “No Flow” Mode of Operation (Fig. 2)
If the flow switch will be used to actuate a signal,
alarm or other device when

no flow occurs, connect

the wire from that device to the “N.C.” contact.
Connect the “Hot” power supply wire to “C” terminal.
NOTE: Repeat above to connect wires to second
switch on “D” model flow switches.

STEP 5 - Testing

Advertising