STEP 2 - Determine the Location of the Flow Switch

a. The flow switch must be installed in the pipe using

a threaded tee connection or welded fitting of
minimum length such as a half coupling. Use a

face or hex bushing to reduce the tee outlet to 1"
(25mm) pipe thread if a reduced tee outlet thread
size fitting is not available.

• The flow switch

should be located in a horizontal

section of pipe where there is a straight horizontal run
of at least 5 pipe diameters on each side of the flow
switch. The flow switch may be installed in a vertical
pipe if the flow is in the upward direction.

• The flow switch

must be installed in the upright

position as shown with arrow mark on side of casting
in the same direction as fluid will flow.

• Some system conditions that require more than 5 pipe

diameters are high viscosity fluid and high fluid velocity.

• The flow switch must be installed in the pump suction

piping when spring-loaded check valves and/or other
close coupled accessories are installed in the pump
discharge piping.

1" (25mm)

1"

(25mm)

1"

(25mm)

Threaded

Pipe

Threaded

Pipe

Threaded

Pipe

Welded

Pipe

b. When installing in brazed/soldered copper pipe,

size the threaded adapter to ensure the paddle
arm extends into the main run of the pipe

STEP 3 - Connecting the Flow Switch to Pipe

FLOW

a. Insert the 8/32 x 1/4" flathead screw through

washer and paddle. Attach screw to opposite side
of the paddle arm’s curve and tighten to a torque
of approximately 12-16 lb•in (1.36-1.81 N•m).

NOTE: If two paddles are being installed, they
must be stacked one on top of the other with the
longer paddle first in line to the flow.

CORRECT

INCORRECT